14.8 General Specifications

Construction

Mounting angle:

Up to 30° of backward tilt angle allowed, no tilt to the left or
right

Mounting panel thickness:

2 to 26 mm

Material:

Case: Steel plate
Bezel: Polycarbonate

Color:

Case: Pale cobalt blue (DIC16-102 or equivalent)
Bezel: Charcoal gray light (Munsell 10B3.6/0.3 or equivalent)

Front panel:

Water and dust-proof (based on IEC529-IP65, and NEMA
No.250 TYPE 4 (except external icing test)

External dimensions:

288(W) × 288(H) × 220(D) mm

Weight (approx.):

CX2010: 6.6 kg, CX2020: 7.0 kg, CX2210: 6.9 kg, CX2220: 7.2 kg,
CX2410: 7.1 kg, CX2420: 7.5 kg, CX2610: 7.4 kg, CX2620: 7.7 kg

I/O Specifications

Control Output
Current output:

Number of outputs: 2 outputs/2 loops
Output signal:

4 to 20 mADC or 0 to 20 mADC

Load resistance:

600 Ω or less

Output accuracy:

±0.1% of span (1 mA or more)

Temperature drift:

±200 ppm/° C (output section)

Voltage pulse output:

Number of outputs: 2 outputs/2 loops
Output signal:

ON voltage = 12 VDC

Load resistance:

600 Ω or more

Resolution:

0.1%

Relay contact output:

Number of outputs: 2 outputs/2 loops
Output signal:

NC, NO, COM

Contact rating:

250 VAC, 3 A or 30 VDC, 3 A (resistive load)

Contact Input
Number of inputs:

6 inputs/2 loops

Input signal:

Non-voltage contact or open collector (TTL or transistor)

Input condition:

ON voltage:

0.5 V or less (30 mADC)

Leakage current when turned OFF:

0.25 mA or less

Input format:

Photocoupler isolation (2 points common)

Contact output
Relay output:

2 outputs/2 loops

Relay contact rating:

250 VAC, 1 A or 30 VDC, 1 A (resistive load)

Transistor output:

4 outputs/2 loops
Transistor contact rating: 24 VDC, 50 mA

Analog Input Section
Control PV input:

Up to 10 inputs (isolated) (the number of inputs varies

depending on the model and control mode)
Period: 250, 500, 1000 ms

Measurement input:

10 or 20 inputs (DCV, TC, and ID are isolated)
Period: 1 s or 2 s