4-7

IM 04L31A01-01E

Control Function Related Setup Operations

4

• Auto1-2 or 3-4 ← selectable only during cascade control.

Select this for internal loops 1-2 or 3-4 when registering a contact input for
switching from cascade operation or manual operation to auto operation.

• Man1-2 or 3-4 ← selectable only during cascade control.

Select this for internal loops 1-2 or 3-4 when registering a contact input for
switching from cascade operation or auto operation to manual operation. A single
registration is possible per control output terminal block. This setting is not allowed
for control output terminal block 3.

• SPNumber0 to 3 bit

Select when registering a contact input for switching the SP. Four contact inputs
(4-bit binary) are used to specify SP numbers [1] to [8]. For example, set
SPnumber1bit and SPnumber2bit to ON to specify SP number [6].
Contact outputs that can be registered to [SPnumber0bit] to [SPnumber3bit] are
[DI003 to DI006] of loop 1 and 2 control output terminal block and [RI009 to RI012]
of the control DIO expansion terminal block. Only the required number of bits can
be registered. For example, if you are switching among SP numbers [1] to [3],
register only [SPnumber0bit] and [SPnumber1bit] (2 bits).
If [SPnumber0bit] through [SPnumber3bit] that corresponds to the MSB is set to
[DI006] of loop 1 and 2 control output terminal block or [RI012] of the control DIO
expansion terminal block, the required number of bits of contact inputs—[DI003 to
DI006] for the control output terminal block, [RI009 to RI012] for the control DIO
expansion terminal block—are automatically registered.

Note

For contact inputs [SPnumber0bit] to [SPnumber3bit], the loop number for which the SP

number is to be switched can be selected. For the operating procedure, see the

explanation for [SP No. selection source] on

page 4-8

.

Only a single system of SP assignment using contact inputs is available on each CX2000.

• ProgramRun ← selectable only during program control

Select to register a contact input for starting the program operation.

• ProgramReset ← selectable only during program control

Select to register a contact input for resetting the program operation.

• Hold ← selectable only during program control

Select to register a contact input for holding the program operation.

• Advance ← selectable only during program control

Select to register a contact input for advancing the program operation.

• PatternNo0 to 4bit ← selectable only during program control

When registering as a contact input for switching the program pattern.
When specifying program pattern numbers in binary
5 contact inputs (5-bit binary) are used to specify the pattern number (1 to 30). For
example, set [PatternNo1bit] and [PatternNo2bit] to ON to specify pattern number [6].
Contact outputs that can be registered to [PatternNo0bit] to [PatternNo4bit] are
[DI001 to DI005] and [DI201 to DI205] of the control output terminal block and
[RI001 to RI005] of the control DIO expansion terminal block. Only the required
number of bits can be registered. For example, if only 2 bits are needed to make
the switch, register only [PatternNo0bit] and [PatternNo1bit].
If you place the cursor on [DI001] (with the control output terminal block) or [RI001]
(with the control DIO expansion terminal block) and press the soft key that includes
the maximum pattern number to be specified, contact inputs of the required
number of bits, [DI001]-[DI005] (control output terminal block) or [RI001]-[RI005]
(control DIO expansion terminal block), are automatically registered.
When specifying program pattern numbers in binary-coded decimal (BCD)
(version 3.20 or later)
For the setting procedure, see section 4.19, “Settings for Switching the Program
Patterns Using Contact Inputs with BCD Codes (Version 3.20 or Later).”

4.2 Control > DI/DO/SW-registration/AUX (Alarm mode...)