Wiring procedure, Measurement input wiring – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 135

Advertising
background image

2-18

IM 04L31A01-01E

When using the reference junction compensation of the CX2000 through thermocouple
input, take measures to stabilize the temperature at the terminal section.
• Always attach the terminal cover.
• Do not use thick wires with high heat radiations effects (cross-sectional area of 0.5

mm

2

or smaller recommended).

• Keep the ambient temperature consistent. Large temperature fluctuations can occur

as a result of such things as turning ON/OFF a nearby fan.

To protect the control current output/voltage pulse output section from external
noise such as electrical serges, it is recommended that an external serge
protector (such as AR-SA (for current output) or AR-LP (for volrage pulse output)
by Yokogawa M&C Corporation) be connected.

Connecting the input wires in parallel with other instruments may mutually affect
the measured values.
If you need to make a parallel connection:
• Turn OFF burnout.
• Ground each instrument at a single common point.
• Do not turn ON/OFF the instrument during operation. It may cause adverse affects on

other instruments.

• Resistance temperature detectors cannot be connected in parallel.

Wiring Procedure

1. Turn OFF the power to the CX2000 and remove the terminal cover.
2. Wire the signal wires to the terminals.
3. Attach the terminal cover and secure it with screws.

Measurement Input Wiring

DC voltage input, DI (ON/OFF) input

• Thermocouple input

• DC voltage input, DI (ON/OFF) input

• RTD input

• DC current input

DC current input

Shunt resistor
Example: For 4 to 20 mA input,
shut resistance values should be
250
Ω ±0.1%.

+

Lead wire resistance
per wire of 10
or less.

Make the resistance of
the three wires equal.

A

b

B

Compensation lead

b

A

B

b

A

B

b

A

B

b

A

B

+

Note

On the standard measurement input block, RTD input terminals A and B are isolated on each

channel. Terminal b is shorted internally across all channels. If you specified the three-wire

isolated RTD (/N2) option, b terminals are isolated with each other.