Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 39

Advertising
background image

1-27

IM 04L31A01-01E

Explanation of Functions

3

2

1

4

5

6

7

8

9

10

11

12

13

14

Contact Input Information Registration
You can select the information that is registered to the contact input from the following.

Name of Action

Detection

Action

Stop all loop control operation

Trigger

Stops the operation of all internal loops.

Start all loop control operation

Trigger

Starts the operation of all internal loops.

Stop/run control (loops 1 to 6)

Edge

Starts/stops the operation of each internal loop.

Remote/local (loops 1 to 6)

Edge

Switches the local/remote operation modes of each
internal loop.

Auto/Man operation

Edge

Switches the auto/manual operation modes of each

(loops 1 to 6)

internal loop.

Cascade switching

Trigger

Switches the internal loops 1-2 and internal loops

(loops 1-2, 3-4)

3-4 to cascade operation.

Auto operation

Trigger

Switches the internal loops 1-2 and internal loops

(loops 1-2, 3-4)

3-4 to auto operation.

Manual operation

Trigger

Switches the internal loops 1-2 and internal loops

(loops 1-2, 3-4)

3-4 to manual operation.

Set target setpoint bits 0 to 3

Trigger

Switches the SP to the specified binary value.

Start program operation

Trigger

Starts the program operation (only on models with the
program control option).

Reset program operation

Trigger

Resets the program operation (only on models with the
program control option).

Hold

Trigger

Holds the program operation (only on models with the
program control option).

Advance

Trigger

Advances the program operation (only on models with the
program control option).

Set pattern number 0 to 4 bits

Trigger

Switches the program pattern number to the specified
binary or binary-coded decimal value (only models with the
program control option).

Input switch contact

Edge

Switches the PV input (PV1, PV2) of each internal

(loops 1 to 4)

loop during loop control with PV input switching.

Start/Stop

Edge

Starts/stops data acquisition to the internal memory.

Trigger

Trigger

Trigger used to start acquiring event data to the
internal memory (valid only when “event data” is
specified to be acquired to the internal memory and
the trigger used to start the acquisition is set to
“external trigger”).

Alarm ACK

Trigger

Clears alarm display/relay output (valid only when the
alarm indicator or output relay behavior is set to “hold”).

Time adj

Trigger

Adjusts the internal clock to the nearest hour.

Math

Edge

Starts/stops computation (only on models with the
computation function (/M1)).

Math reset

Trigger

Resets computed data of measurement channels
(Resets the computed value to 0. Only when
computation is stopped on models with the
computation function option).

Manual sample

Trigger

Acquires instantaneous values of all channels to the
internal memory.

Load setup data 1 to 3

Trigger

Loads the setup data file saved to the external storage
medium.

Messages 1 to 8

Trigger

Displays message 1 to 8 on the trend display and
stores the message to the internal memory.

Snapshot

Trigger

Saves the screen image data to the external storage
medium.

Method of Detecting Contact Inputs
The above operations are carried out on the rising or falling edge of the contact signal
(edge) or the ON signal lasting at least 250 ms (trigger). The remote signal rises when
the contact switches from “open to closed” and falls when the contact switches from
“closed to open.” For open collector signals, the remote signal rises when the collector
signal (voltage level of the input terminal) goes from “high to low” and falls when the
collector signal goes “low to high.”

Rising and falling edges

Trigger

Rising

Falling

250 ms or more

1.5 Contact Input/Output Related Settings

Advertising