Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 288

Advertising
background image

9-4

IM 04L31A01-01E

• Block

Select the number of blocks when dividing the event data acquisition area into
blocks. Select from [2], [4], [8], and [16]. Select [1] if you do not wish to divide the
area into blocks. When acquiring both display data and event data, the possible
selections are [1], [2], and [4].

• Data length

Set the size (data length) of a single block of the event data acquisition area in terms of the
amount of time data is to be acquired. The selectable data length varies depending on the
sampling interval (sample rate setting) as shown in the table below. It also depends on the
block setting and the number of measurement/computation channels.

Sampling

1

2

5

10

30

60

120

300

600

interval (s)

Data length 3min

3min

(choices)

5min

5min

10min 10min

10min

10min

20min 20min

20min

20min

30min 30min

30min

30min

1h

1h

1h

1h

1h

1h

1h

1h

1h

2h

2h

2h

2h

2h

2h

2h

2h

2h

3h

3h

3h

3h

3h

3h

3h

3h

3h

4h

4h

4h

4h

4h

4h

4h

4h

4h

6h

6h

6h

6h

6h

6h

6h

6h

6h

8h

8h

8h

8h

8h

8h

8h

8h

8h

12h

12h

12h

12h

12h

12h

12h

12h

12h

1day

1day

1day

1day

1day

1day

1day

1day

1day

2days

2days

2days

2days

2days

2days

2days

2days

3days

3days

3days

3days

3days

3days

3days

5days

5days

5days

5days

5days

5days

5days

7days

7days

7days

7days

7days

7days

10days 10days 10days 10days 10days 10days

14days 14days 14days 14days 14days

31days 31days 31days 31days

• Pre-trigger

Select the range when saving the data existing before the trigger condition is met
as event data. Select the range as a percentage of the data length from [5], [25],
[50], [75], [95], and [100]%. If you do not wish to acquire the data existing before
the trigger condition is met, select [0]%.

• Trigger

Set the trigger condition used to acquire the event data.

• Key

Select [On] if you wish to activate the trigger using key operation.

• External

Select [On] if you are applying the trigger signal through remote input.

• Alarm

Select [On] if you wish to use alarm occurrences as triggers.

Setting Memory and Trend (Setting the Channels for Saving Data)

• Meas/Math/Loop CH

Select the type of target channels from [Meas CH], [Math CH], [Int CH] (PV input of
internal control loops), [Ext CH] (PV input of external control loops),

• First-CH/Last-CH

Set the range of channels to turn [On/Off] depending on the type of target channels.
Meas CH: 01 to 20 ([01] to [10] on models with 10 measurement channels)
Math CH: 31 to 60 (selectable only on models with the computation function option (/M1)
Int CH:

101 to 118 (The maximum channel number varies depending on the
maximum control loop)

Ext CH:

201 to 248

9.1 Acquiring Measurement Data to the Internal Memory and Saving Data to the External Storage Medium