14.2 Control Function

General Control Functions

Control Mode
Select from three controls for every two loops: single loop control, cascade control, and loop
control with PV switching (however, only single loop control is possible on loops 5 and 6).
Control Computation Function
Continuous PID control, on/off control, time proportional PID control
PID control:

PID Control

Method

PV derivative

type PID

Deviation

derivativ type PID

PV derivative

type PID

Deviation

derivative type PID

PV derivative

type PID

PV derivative

type PID

PV derivative

type PID

PV derivative

type PID

Local and not the secondary side of a cascade
connection
Remote or secondary side of a cascade
connection
Local and not the secondary side of a cascade
connection or hold or soak
During program control (excluding hold and soak)
or the secondary side of a cascade connection
Local and not the secondary side of a cascade
connection
Remote or secondary side of a cascade
connection
Local and not the secondary side of a cascade
connection or hold or soak
During program control (excluding hold and soak)
or the secondary side of a cascade connection

PID control

mode

Standard

PID

control mode

Fixed-point

control mode

Operation

mode

Fixed-point

control

operation

Program

control

operation

Fixed-point

control

operation

Program

control

operation

Control

Output Bump

Yes

Yes

Yes

Yes

No

Yes

No

Yes

*

The secondary side of a cascade connection refers to the secondary loop of which the cascade control

mode is set to Cascade (of the Auto, Manual, and Cascade selections).

Operation Status

PID parameters:

8 sets/loop

Zone PID switch point:

Up to 6

Super function (overshooting suppression): Available
Tracking function:

SP tracking
PV tracking

Anti-reset windup (over-integration prevention)
Control period:

250, 500, 1000 ms

Operation Mode Switching
Remote, local, and program switching
Manual, auto, and cascade switching
Run/stop switching

Stop: Outputs the preset output

Auto tuning enable/disable switching

Principle: Limit cycle method

Selectable Range of Control Parameters
Proportional band:

0.1 to 999.9%

Integral time:

0 to 6,000 s

Derivative time:

0 to 6,000 s

On/Off control hysteresis width:

0.0 to 100.0% of the measurement span

Preset output:

–5.0 to 105.0% of the control output (output when control
computation is stopped, when PV input is burned out, and
when measurement input is erroneous)

Selectable range of high/low limit of the output limiter:

–5.0 to 105.0% of measurement span

Shutdown function:

Output up to 0 mA of control output during manual operation at
4 to 20 mA output (shutdown at less than or equal to –5.1%)

Output Velocity Limiter:

Off or 0.1 to 100.0%/s