4-44

IM 04L31A01-01E

Setup Item

Logic Computation Settings

• Setting Numbers

Up to 30 logic computations can be set. Select the numbers for the logic
computations.

• Relay

Select the destination for the computed results.
DO001-DO006:

Control output terminal block DO (for loops 1 and 2)

DO101-DO106:

Control output terminal block DO (for loops 3 and 4)

DO201-DO206:

Control output terminal block DO (for loops 5 and 6)

RO001-RO012:

Control DIO expansion terminal block DO

SW001-SW036:

Internal switches

• Equation

Follow the instructions in the equation pop-up window to enter the equation (using
120 characters or less). The number of data that can be used in equations is 35. You
can also use the control constants W01-W36 in the equation. Measurement
constants K01-K36 cannot be used.
You can use the following operators.

Computation Type

Operator

Logical operation

AND, OR, XOR, NOT

Relational operation

.GT., .LT., .GE., .LE., .EQ., .NE.

Conditional expressions

[eq1?eq2:eq3]

See appendix 3, “Meanings and Syntax of Equations” for information on how to create
equations.

4.17 Logic Computation Settings (Style Number S3 or Later)