IM 04L31A01-01E

1.6

Target Setpoint Related Settings

Setting the SP

Set the SP, as one of the PID parameters, for each PID number (1 to 8) in the range of
EU (0.0 to 100.0% of the measurement span). The PID number in which the SP has
been registered is handled as “SP number” when specifying the setpoint and for other
purposes.

SP Assignment

The SP is specified using the SP number. The operation at the time of SP number
switching varies depending on the PID selection method.
• When target setpoint selection method is selected

The SP number and PID number are synchronized. By switching the SP number, the
control parameters (“PID parameters” in the settings) such as the SP and the PID
constant are changed to the control parameters registered to the corresponding PID
number.

SP1

(No.1PID)

SP3

(No.3PID)

SP1

(No.1PID)

SP2

(No.2PID)

PV

Rise according to

the setpoint

ramp-up setting

SPn: SP number

Rise according to
the setpoint
ramp-up setting

Switch from SP1 to SP3

Switch from SP3 to SP1 Switch from SP1 to SP2

Time

Fall according to
the setpoint
ramp-down setting

• When zone PID method is selected

The assignment of the SP number and the assignment of the PID number are not
synchronized.
A PID number (group number of the PID parameter) is registered for each zone
beforehand. When the PV changes and becomes a value of a different zone, the PID
number automatically changes, but the SP number does not switch.

Note

The value of control alarms corresponds to the SP number (see

section 4.7

). If the SP

number is changed, the alarm value also changes accordingly.

Selection of the SP Number to Be Switched Using Contact Input

Set loop 1 to 6 for switching the SP number using the contact input “Set target setpoint
bits 0 to 3” (see page 1-27).

Target Setpoint Tracking

The CX2000 can perform operation according to the remote SP (remote input) received
from an external source. In this case, it is foreseeable that the output value will
drastically change when switching from a remote operation condition to a local operation
(operation according to the internal SP of the CX2000) condition or switching from
program operation to local operation. To prevent the output value from drastically
changing, the CX2000 has a function used to track the output from the remote SP to the
local SP. The operation image of target setpoint tracking is shown below.

PV

Local SP

Remote SP

• When target setpoint tracking is enabled

Switch from remote to local mode

Time

Time

• When target setpoint tracking is disabled

Switch from remote to local mode

Local SP

Remote SP

PV