Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 209

Advertising
background image

4-49

IM 04L31A01-01E

Control Function Related Setup Operations

4

• Procedure

1. Use the

arrow keys

to move the cursor (blue) to the [Module] box.

A soft key menu is displayed at the bottom of the display.

2. Press the

soft key

corresponding to the terminal block to be used.

The box for the item you changed turns yellow, and the cursor moves to the next
item.

3. Press the

soft key

corresponding to the program pattern number to be used.

The box for the item you changed turns yellow, and the cursor moves to the next
item.

4. Press the

DISP/ENTER key

to confirm the changes.

The boxes for the items you changed turn from yellow to white, and the cursor
returns to the first item box.

• Save the Settings in Basic Setting Mode

1. Press the

ESC key

.

The display returns to the basic setting menu.

2. Press the

[End] soft key

.

A confirmation dialog box appears.

3. Select [Yes] and press the

DISP/ENTER key

.

The operation screen is displayed.

Setup Items

For each of the settings other than BCD code contact input registration, see section 4.2,
“Basic Control Settings > DI/DO/SW Registration, AUX (Alarm Mode...).”
DI/DO/SW-registration
Press the soft key corresponding to the program pattern number to specify.

1

1

2

Up to 3

3

Up to 7

4

Up to 9

5

Up to 19

6

[Ptrn 1] soft key

[Ptrn 1 - 3] soft key

[Ptrn 1 - 7] soft key

[Ptrn 1 - 15] soft key

[Ptrn 1 - 30] soft key
[Ptrn 1 - 30] soft key

[Patrn 1] soft key

[Patrn 1 - 3] soft key

[Patrn 1 - 7] soft key

[Patrn 1 - 15] soft key

[Patrn 1 - 30] soft key
[Patrn 1 - 30] soft key

Up to 30

Required Number
of Bits (BCD)

Setup Procedure

CX1000

CX2000

Program Pattern
Number Used

Be sure to set [None] for the [PatternNo5bit]
position.

If you place the cursor on [DI001] (with the control output terminal block) or [RI001] (with
the control DIO expansion terminal block) and press the soft key that includes the
maximum pattern number to be specified, contact inputs of the required number of bits,
and [DI001]-[DI005] (control output terminal block) or [RI001]-[RI005] (control DIO
expansion terminal block) are automatically registered.

4.19 Settings for Switching the Program Patterns Using Contact Inputs with BCD Codes (Version 3.20 or Later)