Appendix 6 initial values, Appendix 6, Basic setting mode – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 392

Advertising
background image

App-23

IM 04L31A01-01E

Appendix

App

Appendix 6 Initial Values

Basic Setting Mode

#1 Alarm,A/D,Temperature

Parameter

Initial Value

Alarm > Reflash

Off

Alarm > Relay > AND

None

Alarm > Action

Energize

Alarm > Behavior

Nonhold

Alarm > Indicator

Nonhold

Alarm > Rate of change > Increase/Decrease

1

Alarm > Hysteresis

On

A/D Integrate > Integrate

Auto

A/D > Scan interval

1 s

A/D > First-CH

01

A/D > Last-CH

01

A/D > Burnout set

Off

A/D > RJC

Internal

Temperature > Unit

C

#2 Memory,Memory and trend,Memory timeup

Parameter

Initial Value

Memory > Save

Auto

Memory > Data

Display

Memory and trend > Meas/Math/Loop CH

Meas CH

Memory and trend > First-CH

01

Memory and trend > Last-CH

01

Memory and trend > On/Off

On

Memory timeup > Timeup type

Off

#3 Keylock

Parameter

Initial Value

Keylock > Use/Not

Not

#4 Key login

Parameter

Initial Value

Key login > Use/Not

Not