10-6

IM 04L31A01-01E

Setup Procedure

• Setting the alarm

1. Use the

arrow keys

to move the cursor (blue) to the [First-CH] and [Last-CH]

boxes.

2. Press the

soft key

corresponding to the start and end channel numbers for

setting the alarm.

3. Use the

arrow keys

to move the cursor (blue) to the Math alarm [1] to [4] boxes.

4. Press the

[On] soft key

corresponding to the alarm you wish to select.

[Type], [Value], and [Relay On/Off] entry boxes appear.

5. Use the

arrow keys

to move the each of the entry boxes and select the alarm

type, alarm value, and relay output On/Off using the

soft keys

.

If [Relay On/Off] is set to [On], the [Number] box appears.

6. If [Relay On/Off] is set to [On], select the relay output number from [I01] to [I06],

[D0001] to [D0006], [D0101] to [D0106], [D0201] to [D0206], [R001] to [R012],
and [SW001] to [SW036] using the

soft keys

.

7. Press the

DISP/ENTER key

.

• Setting the alarm delay

1. Use the

arrow keys

to move the cursor (blue) to the [First-CH] and [Last-CH]

boxes.

2. Press the

soft key

corresponding to the start and end channel numbers for

setting the alarm.

3. Use the

arrow keys

to move the cursor (blue) to the [Time] box under Alarm

delay.

4. Press the

[Input] soft key

and set the alarm delay time on the pop-up window.

5. Press the

DISP/ENTER key

.

Setup Items

Math alarm

• Off/On

Four alarms (alarm numbers 1 to 4) can be specified for the selected alarm channel.
Set the desired alarm to [On].

• Type

Select the alarm type from the following four types.
H (High limit alarm):

An alarm occurs when the measured/computed value
exceeds the alarm value.

L (Lower limit alarm):

An alarm occurs when the measured/computed value falls
below the alarm value.

T (Delay high limit alarm): An alarm occurs when the computed value remains above

or equal to the alarm value for the specified delay.

t (Delay low limit alarm):

An alarm occurs when the computed value remains below
or equal to the alarm value for the specified delay.

• Value

Set the value according to the [Type] you selected above. The selectable range is the
range defined by [Span Upper/Lower] that was specified in “Assigning Computation
Channels” (see the previous section).

• Relay On/Off

Select whether to enable [On] or disable [Off] the relay output.

10.3 Setting Computation Channel Alarms