PV/SP Computation Function

Equations for each PV and SP can be set.
Computation type:

General purpose computation:

Arithmetical operations (+, -, *, /),
square root, absolute value, common
logarithm, exponents, power,
relational operations (<, ≤, >, ≥, =, ≠),
and logical operators (AND, OR,
NOT, XOR).

Within group statistics:

Average, max, (CLOG), min, integral
values of data within groups

Conditional expressions: [eq1?eq2: eq3]

Allowed data:

Measured data, measurement computation data, internal/
external control data, communication input data, constants
(W01-W36), control input channel data, control output module/
expansion module DIO, measurement remote input, internal
switches

Constants:

Up to 36 constants can be set

Error processing:

OVER:

Use the upper limit value of the PV range for the PV
and SP value.

UNDER: Use the lower limit value of the PV range for the PV

and SP value.

Logic Computation Function

Computation type:

Relational operations (<, ≤, >, ≥, =, ≠), and logical operators
(AND, OR, NOT, XOR), and conditional expressions
[eq1?eq2:eq3].

Allowed data:

Same as PV/SP computation function

Internal Switches
Allowed number:

36 (SW001-SW36)

Fixed at “nonhold.”

Analog Retransmission Function

Output format:

Current output (4-20 mA, 0-20 mA, 20-4 mA, 20-0A)
Time proportional voltage pulse output, time proportional relay
output

Display/recording:

Displayed as the OUT value, recorded to data file
With loops set in analog retransmission, the PID computation
is not performed.

Computation type:

Same as PV/SP computation function

Allowed data:

Same as PV/SP computation function

14.2 Control Function