Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 179

Advertising
background image

4-19

IM 04L31A01-01E

Control Function Related Setup Operations

4

• When set to Scale

Select the [Type] (input type) from [DCV], [TC], and [RTD]. Then, set the [Range],
[Span Lower/Upper-limit], and the [Scale Lower/Upper-limit] and [Unit] after the
conversion according to the selected [Type]. The selectable range for [TC] and
[RTD] is the same as with the other inputs selected by [Mode]. The selectable
range of the scale is “–30000 to 30000.” The decimal place can be set to
“X.XXXX,” “XX.XXX,” “XXX.XX,” “XXXX.X,” or “XXXXX.” The decimal place is
determined by the scale low limit setting.
• Range and measurable range for voltage input

Range

Selectable Measurement Span Range

20mV

–20.00 to 20.00 mV

60mV

–60.00 to 60.00 mV

200mV

–200.0 to 200.0 mV

2V

–2.000 to 2.000 V

6V

–6.000 to 6.000 V

20V

–20.00 to 20.00 V

50V

–50.00 to 50.00 V

Note

Values such as alarm values are set using engineering units (EU or EUS) based on the

measurement span. For an explanation on engineering units (EU and EUS), see

appendix 8, “Explanation of Engineering Units (EU and EUS).”

For current inputs, a shunt resistor is attached to the input terminal to convert the signal to

voltage input. The following table shows the available shunt resistors. For example, a

250-Ω shunt resistor is used to convert the signal to 1 to 5 V for 4-20 mA input.
Name

Model

Resistance

Shunt resistor

4159 20

250 Ω ± 0.1%

(for screw terminals)

4159 21

100 Ω ± 0.1%

4159 22

10 Ω ± 0.1%

• PV range Lower/Upper-limit

(setting when [Input type] is set to [PVrange] during

loop control with PV switching)
Set the value in the range [–30000] to [30000] (maximum value > minimum value,
maximum value – minimum value ≤ 30000).

• PV switching Lower/Upper limit

(setting when [Input type] is set to [PVrange])

Set the value within the input range. If [Control] > [#1 Control action, Input setting] >
[Method] is set to [Range], set [PV switching Upper/Lower]; if [Method] is set to
[PVHigh], set [PV switching Upper] only.

• Scale Lower/Upper-limit

Set the value in the range [–30000] to [30000] (maximum value > minimum value,
maximum value – minimum value ≤ 30000).

• Unit

You can enter the unit using up to 6 alphanumeric characters.

• Square root

Set whether to perform square root computation on the PV input ([On]/[Off] (initial value)).

• Low-cut

Set the low-cut point when the square root computation is On to [0.0 to [5.0]% (initial
value is 1.0%).

• Bias

Set bias to [On] (initial setting is Off) when adding a constant value (bias) to the PV
input. Set the bias value in the EUS range (–100% to 100%) of the measurement
span. For example, if the minimum and maximum values of the scale are [10.00] and
[200.00], respectively, the selectable range is “–190.00 to 190.00%.” The selectable
range is displayed in a pop-up window. Note that the bias can be changed during
control operation.

4.6 Control input range