Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 73

Advertising
background image

1-61

IM 04L31A01-01E

Explanation of Functions

3

2

1

4

5

6

7

8

9

10

11

12

13

14

Note

For current inputs, a shunt resistor is attached to the input terminal to convert the signal to

voltage input. The following table shows the available shunt resistors. For example, a

250-Ω shunt resistor is used to convert the signal to 1 to 5 V for 4-20 mA input.
Name

Model

Resistance

Shunt resistor

4159 20

250 Ω ± 0.1%

(for screw terminals)

4159 21

100 Ω ± 0.1%

4159 22

10 Ω ± 0.1%

The square-root computation method of the CX2000 is indicated below.

F = (F - F )

x

max

min

V - V

x

min

max

min

V - V

=

min

F

Meanings of the symbols are shown below.

V

min

: span lower limit, V

max

: span upper limit, F

min

: scale lower limit after conversion,

F

max

: scale upper limit after conversion, V

x

: input voltage, F

x

: scaling value.

If the value inside the root is negative, the computed result is displayed as follows.

When F

min

< F

max

: “–*****”

When F

min

> F

max

: “+*****”

Input Range and Measurable Range

When the input type is set to DC voltage, thermocouple, resistance temperature detector,
or ON/OFF input, you will select the range to match the input signal. For DC voltage, select
the measurable range (select [20mV] for “–20.00 to 20.00 mV”). For thermocouple or
resistance temperature detector, select the type. For example, the type selections for the
thermocouple are [R], [S], [B], [K], [E], [J], [T], [N], [W], [L], [U], [PLATINEL], [PR40-20], and
[W3Re/W25Re]. If [R] is selected, the measurable range is 0.0 °C to 176.0 °C. In addition,
you will set the measurement span ([Span lower limit] and [Span high limit]) within the
measurable range as the actual range for making measurements.

Burnout Detection

When measuring the temperature using a thermocouple, you can have the measurement result
set to positive overrange

*1

or negative overrange

*2

when a burnout occurs. Burnout can be set

on each measurement channel. The initial setting is set so that burnout is not detected.

*1 Positive overrange refers to the condition in which the input signal is exceeding the upper limit of

the measurable range of the input range. The measured value is show as “+*****”.

*2 Negative overrange refers to the condition in which the input signal is less than the lower limit of

the measurable range of the input range. The measured value is show as “–*****”.

Reference Junction Compensation

When measuring the temperature using a thermocouple, the reference junction compensation
can be used. You can select whether to use the reference junction compensation provided by
the CX2000 or an external reference junction compensation. If you are using an external
reference junction compensation, you will also set the reference voltage. The initial setting is set
so that the reference junction compensation provided by the CX2000 is used. When using the
external reference junction compensation, set an appropriate reference junction
compensation voltage. As in the example in the following figure, if the reference junction
temperature for the external reference junction compensation is T

0

°C, set the

thermoelectromotive force of the 0-°C reference for T

0

°C as the reference junction

compensation voltage.

CX2000

External reference junction compensation
(Hold the contact point of the thermocouple
and copper wire at T0
°C)

Thermocouple

Copper wire

1

2

3

4

DISP/

ENTER

1.14 Measurement Function > Measurement Input Related Settings