Operations during Control Operation

6

Executing and Releasing the Hold Operation

1. Press the

[HOLD] soft key

.

A pop-up window for executing/releasing the hold operation appears.

2. Select [ON] (execute) or [OFF] (release) using the

up and down arrow keys

.

3. Press the

DISP/ENTER key

to confirm the changes.

To close the window without making any changes, press the ESC key.

Changing the Remaining Segment Time When in Hold Operation

1. Press the

[SEG TIME] soft key

.

A pop-up window for changing the remaining segment time appears. The window
shows the remaining segment time.

2. Change the remaining segment time using the

up and down arrow keys

.

3. Press the

DISP/ENTER key

to confirm the changes.

To close the window without making any changes, press the ESC key.

Changing the Target SP When in Hold Operation

1. Press the

[TSP CHG] soft key

.

A menu for selecting the loop of which the target SP is to be changed appears.
The soft keys of each loop show the tag names of each loop ([INT-01] to [INT-06]
in the figure below).

2. Press the

soft key

corresponding to the tag name of the loop you wish to change

the target SP.
A pop-up window for changing the target SP appears. The window shows the
current target SP.

3. Change the target SP using the

up and down arrow keys

.

4. Press the

DISP/ENTER key

to confirm the changes.

To close the window without making any changes, press the ESC key.
Press the [BACK] soft key to return to the original soft key menu.

Turning ON/OFF the Pattern Waveform Display of Each Loop

The operation is the same as program selection display. For the operating procedure,
see page 6-12.

Event Display Operation (Style Number S3 or Later)

The operation is the same as program selection display. For the operating procedure,
see page 6-13.

ALL

Currently occurring events are displayed in red,
non-occurring events are displayed in green

PV events, events that already
occurred, are displayed

Shows upper and lower limit values
when events are displayed

Event display

Pattern display

Time events, even those occurring
from this point, are displayed

Time events

PV events

6.4

Operations on the Program Selection Display and Program Control Display (Only on Models with the

Program Control Option)

Advertising