Terminal cover labels, For the control dio expansion terminal block, 3 wiring – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 125

Advertising
background image

2-8

IM 04L31A01-01E

Note

There are no output registration settings for the FAIL and MEMORY terminals. However,

the setting for outputting memory end, Memory Alarm Time, exists. In addition, FAIL

output can be assigned to the DIGITAL OUT1 terminal of the loop 1 and 2 control output

terminal block. In this case, registration settings are required.

The control alarm output cannot be assigned to the [ALARM] terminal. The control alarm

output can be assigned to the DIGITAL OUT terminal of the control output terminal block

and the control extension DIO terminal block. The measurement alarm output can be

assigned to the DIGITAL OUT terminal of the control output terminal block and the control

extension DIO terminal block.

Terminal Arrangements of the Measurement Input Terminal Block
Ten measurement input terminals are available on each terminal block as shown in the
following figure.

• For CH1 to 10

b

A

B

1

b

A

B

2

b

A

B

3

b

A

B

4

b

A

B

5

b

A

B

6

b

A

B

7

b

A

B

8

b

A

B

9

b

A

B

10

Channel number

• For CH11 to 20

b

A

B

11

b

A

B

12

b

A

B

13

b

A

B

14

b

A

B

15

b

A

B

16

b

A

B

17

b

A

B

18

b

A

B

19

b

A

B

20

Channel number

Note

In the terminal arrangement diagram of the standard terminal block shown above, b terminals

are shorted with each other. If you specified the three-wire isolated RTD (/N2) option, b

terminals are isolated with each other.

Terminal Cover Labels

A label showing the arrangement of the terminals is affixed to the front and back of the
terminal cover of each terminal block.
Label on the Front of the Terminal Cover
The terminal numbers for checking the connection (not the numbers used in the settings)
are written on the label on the front of the terminal cover (see the following figure).
• For the 6 loop analog control input terminal block

LOOP5

004

005

006

007

008

009

010

011

012

013

014

015

016

017

018

019

020

021

022

023

024

025

026

027

028

029

030

031

032

033

LOOP1

LOOP4

LOOP2

LOOP3

LOOP6

CAT

• For the control DIO expansion terminal block

CAT

D I G I T A L I N

604

605

606

601

602

603

607

608

609

610

611

612

619

620

622

623

625

626

628

629

631

632

634

635

D I G I T A L O U T

613

614

615

636

633

630

627

2.3 Wiring

Advertising