Errors related to ftp client – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 336

Advertising
background image

12-5

IM 04L31A01-01E

12

Troubleshooting

• Errors Related to FTP Client

For information regarding the FTP client function of the CX2000, see the DAQSTATION
CX1000/CX2000 Communication Interface User’s Manual (IM 04L31A01-17E)

. The

detail code does not appear in the error message on the screen. You can view the code
on the FTP log display of the CX2000 or using the FTP log output via communications.

Code

Message

280

IP address is not set or FTP function is not available.

Further details are provided by the character string that appears after error code 280.

Character String and Details

HOSTADDR

The IP address of the CX2000 has not been specified.
Check the IP address.

*1

DORMANT

Internal processing error.

*2

LINK

Data link is disconnected.
Check the cable connection.

281

FTP mail box operation error.

Further details are provided by the character string that appears after error code 281.

Character String and Details

MAIL

Internal processing error.

*2

STATUS

Internal processing error.

*2

TIMEOUT

Internal processing error.

*2

PRIORITY

Internal processing error.

*2

NVRAM

Internal processing error.

*2

282

FTP control connection error.

Further details are provided by the character string that appears after error code 282.

Character String and Details

HOSTNAME

Failed the DNS lookup (search the IP address corresponding to the host name).
Check the DNS setting and the destination host name.

*1

TCPIP

Internal processing error.

*2

UNREACH

Failed to connect to a control connection server.
Check the address setting and that the server is running.

OOBINLINE

Internal processing error.

*2

NAME

Internal processing error.

*2

CTRL

The control connection does not exist.
Check that the server does not drop the connection and that it responds within the proper time period.

IAC

Failed to respond in the TELNET sequence.
Check that the server does not drop the connection and that it responds within the proper time period.

ECHO

Failed to transmit data on the control connection.
Check that the server does not drop the connection and that it responds within the proper time period.

REPLY

Failed to receive data on the control connection.
Check that the server does not drop the connection and that it responds within the proper time period.

SERVER

The server is not in a condition to provide the service.
Check that the server is in a condition in which service can be provided.