2.6

Transmitter Power Supply Wiring (/TPS4
Option)

NING

WARNING

• To prevent the possibility of electric shock when wiring, confirm that the power

supply source is turned OFF.

CAUTION

• Do not short the transmitter power supply output terminal or apply external

voltage to it. This may cause damage to the CX2000.

• Do not use current that exceeds the maximum output current (25 mADC). This

may cause damage to the CX2000.

• To prevent fire, use signal wires having a temperature rating of 70°C or more.

Output Specifications

Number of loops:

4

Output voltage:

22.8 to 25.2 V (under rated load current)

Rated output current:

4 to 20 mADC

Maximum output current: 25 mADC (overcurrent protection operation current: approx.

68 mADC)

Maximum length of cable: 2 km (when using the CEV cable)

Connection

To use the transmitter output as a measurement input, connect the CX2000 and
transmitter as shown below.

+

+

Transmitter

Current

CX2000

Transmitter
power supply
output terminal

Measurement
input terminal

Shunt resistor: 250

Terminal Position

Arrangement Position of Terminal Block

Transmitter power supply

output terminal block

(/TPS4 option)