Repeat function – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 64

Advertising
background image

1-52

IM 04L31A01-01E

Repeat Function

This function repeats the operation over a section of the program pattern consisting of
continuous segments. To perform repeat operation, you specify the repeat start
segment, repeat end segment, and the number of repetitions (repeat count).
Below is a program pattern in which the repeat count = 1, repeat start segment number = 3, and
repeat end segment number = 5. You can also specify an infinite number of repetitions.

TSP1

TSP2

SEG4

SEG6

SEG5

SEG3

SEG5

SEG4

SEG3

SEG2

SEG1

Repeat period: repeat count = 1

Repeat start

segment number = 3

Repeat end

segment number = 5

TSPn: Final target setpoint

Program pattern for

the 2nd loop

Program pattern for
the 1st loop

Same value

Note

The operation when repeat action, repeat start segment, repeat end segment, and repeat

frequency (including infinity) are changed during program control is indicated below.

When changed to repeat OFF or when the segment number at that point is larger than

the repeat end segment

Repeat action is not performed regardless of the repeat action performed (or not

performed) up to that point.

When the segment number at that point is smaller than the repeat start segment

Repeat action is performed from the first repetition using the new settings regardless of

the repeat action performed (or not performed) up to that point.

When the segment number at that point is between the repeat start segment and

repeat end segment

If the change is made before the repeat action is performed (including a change from

repeat OFF) or after the repeat action has been finished, repeat action is performed from

the first repetition using the new settings. If the change is made during repeat action, the

repeat action is performed the number of times specified by the new repeat frequency

including the number of repetitions that have been performed before the change. If the

new repeat frequency is smaller than or equal to the number of repetitions that have

been performed already before the change, the repeat action is terminated after the

current repetition. However, if the repeat frequency is changed from infinity to a finite

value, repeat action is started using the new repeat frequency from the change point.

Only a single period of repeat action can be specified for each program pattern.

Set the first SP of the repeat start segment the same as the last SP of the repeat end

segment. If they do not match, the start segment pattern will be affected.

In repeat action, all time events that are ON are turned OFF when returning from repeat end

segment to repeat start segment. If “time-prioritized PV start” or “ramp-prioritized PV start” is

specified as a starting condition of the program operation, PV start is also performed when repeat

operation is started. However, PV start does not apply to loops in local mode or loops that are

stopped. In cascade control, PV start does not apply if the primary loop is in local mode or the

secondary loop is stopped. If PV start cannot be carried out, “starting target setpoint start” is

carried out.

1.11 Program Control Related Settings