• When Setting the Moving Average

The moving average setting cannot be entered on 0 measurement channel models
(the setting menu is not displayed).
Press the keys in the following sequence:

MENU key

(switch to the Setting mode (Control)) >

MENU key

(switch to the Set

mode) >

#2 soft key

(select [Tag, Moving average, Alarm delay])

The following display appears.

Setup Procedure

1. Use the

arrow keys

to move the cursor (blue) to the item box you wish to change.

A soft key menu is displayed at the bottom of the display.

2. Press the

soft key

corresponding to the value you wish to select.

The box for the item you changed turns yellow, and the cursor moves to the next
item.

3. Repeat steps 1 and 2 to change the value of all the items you wish to change.

Note

The value is set using the pop-up window that appears by pressing the [Input] soft key.

4. Press the

DISP/ENTER key

to confirm the changes.

The boxes for the items you changed turn from yellow to white, and the cursor
returns to the first item box.

Saving the Settings in Basic Setting Mode

1. Press the

ESC key

.

The display returns to basic setting menu.

2. Press the

[End] soft key

.

A confirmation dialog box appears.

3. Select [Yes] and press the

DISP/ENTER key

.

The operation screen is displayed.

Setup Items

Setting the A/D Integral Time, Scan Interval, Etc.

• Integrate

(common to the control input and measurement input)

Select the integral time of the A/D converter. Select from [Auto], [50Hz], [60Hz], and
[100ms].
Auto:

The CX2000 automatically detects the power supply frequency and switches
between 16.7 ms (60 Hz) or 20 ms (50 Hz).

50Hz: The integral time is fixed to 20 ms.
60Hz: The integral time is fixed to 16.7 ms.
100ms: The integral time is fixed to 100 ms (the scan interval is 2 s).

• Scan interval

You can select [1s] or [2s]. However, if Integrate is set to [100ms], the scan interval is
fixed to [2s] ([1s] cannot be selected).

7.1 Settings Related to Measurement Inputs