9-9

IM 04L31A01-01E

Data Save/Load Operations

9

Note

If you attempt to load the setup data and the external storage medium does not contain the

setup data, a message “There is no setting file” appears.

Operations on the Display

• Saving Setup Data

1. Enter the file name in the [File name] box (up to eight characters).
2. Press the

DISP/ENTER key

.

The setup data is saved to the external storage medium. The saved file is
displayed in the file list section on the right side.
If the file with the same name exists on the external storage medium, a
message confirming file overwrite appears. To overwrite the file, select [Yes]
and press the DISP/ENTER key.

• Loading Setup Data

1. Select the file to be loaded from the file list of the external storage medium using

the

up and down arrow keys

.

2. Press the

DISP/ENTER key

.

The setup data is loaded. When the data is loaded, the settings are changed,
and the CX2000 returns to the operation display.

Setup Items

Saving Setup Data
• All the setup data of both modes (setting mode and basic setting mode) are stored.
• Set the file name using up to 8 characters. The following character strings cannot be

used.
AUX, CON, PRN, NUL, CLOCK, and strings containing spaces.

• A .pcl extension is automatically added to the file name of the setup data.
• The size of a setup data file is approximately 200 KB (approximately 70 KB if no

program control settings are present) at maximum.

Loading Setup Data
• Loading the setup data in basic setting mode loads all of the setup data of Set mode

and basic setting mode. Loading the data in Set mode loads only the setup data of
Set mode.

• If the contents of the loaded setup data are invalid, refer to the error message log that

appears by pressing the FUNC key and soft keys. For the procedure of displaying the
error message log, see section 11.4, “Displaying Logs (Checking Operations) and
System Information Display (Checking the System Specifications).”

• A .pcl extension is automatically added to the file name of the setup data.

Precautions to Be Taken When Loading Setup Data
As a general rule, load setup data of the same firmware version. If you must load setup
data of different versions, note the following points.
• When loading setup data that has been saved on version 3.01 using version

3.02
Event output settings (time event, PV event, and program pattern end signal settings)
in Setting mode (Control) are not loaded.

• When loading setup data that has been saved on version 3.02 using version

3.01
• Event output setting (common or separate) in Basic Control Settings is not loaded.
• Event output settings (time event, PV event, and program pattern end signal

settings) in Setting mode (Control) are not loaded.

• Setup data is not loaded when the displayed language is set to Chinese.

9.3 Saving and Loading Setup Data