Contact input (digital in/remote) wiring – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 136

Advertising
background image

2-19

IM 04L31A01-01E

Installation and Wiring

3

2

1

4

5

6

7

8

9

10

11

12

13

14

Contact Input (DIGITAL IN/REMOTE) Wiring

• Relay contact input

2

1

4

6

3

5

C

1

2

3

4

5

6

C

• Transistor input

Control output terminal block (DIGITAL IN)

• Relay contact input

C

C

C

• Transistor input

7

8

9

10

11

12

1

2

3

4

5

6

C

C

C

Control expansion DIO terminal block (DIGITAL IN)

7

8

9

10

11

12

1

2

3

4

5

6

Measurement remote input (REMOTE) of the measurement alarm option terminal block
(/A6R, /A4FR)

C

1

2

3

4

5

6

7

8

• Transistor input

• Relay contact input

C

1

2

3

4

5

6

7

8

Relay Contact Input and Transistor Input Specifications
Input signal:

Non-voltage contact, open collector

Input conditions:

0.5 V or less (30 mADC) when turned ON, leakage current of 0.25
mA or less when turned OFF

Input format:

Photocoupler isolation (shared common)

Withstand voltage: 500 VDC for 1 minute (between the input terminal and earth)

Contact Output (ALARM, FAIL, MEMORY of the Measurement Alarm Option Terminal
Blocks) Wiring

C

NO

NC

250 VAC/3A,

250 VDC/0.1 A(resistive load)

Relay Output Specifications
Output format:

Relay contact

Contact rating:

250 VAC (50/60 Hz)/3 A or 250 VDC/0.1 A (resistive load)

2.3 Wiring

Advertising