1-37

IM 04L31A01-01E

Explanation of Functions

3

2

1

4

5

6

7

8

9

10

11

12

13

14

Output Velocity Limiter

This function is used to prevent radical changes in the control output to protect the
control element and object of control. Since this function negates the derivative action,
use caution when using this function on derivative type control.
Selectable range of velocity: 0.1 or 100.0%/s

1.8 Control Output Suppression Settings