PV Event
This function outputs preset alarms such as PV alarms and deviation alarms during
program operation. PV events operate only within the specified segment.
The following table shows the types of PV events. Hysteresis can be specified for each event.

Alarm

setpoint

Close

Hysteresis

Process

value

Open

Close

Hysteresis

Open

Hysteresis

Open

SP

Deviation
setpoint

Close

Open

Hysteresis

Close

Relay action

(Open/close: relay contact status)

Relay action

(Open/close: relay contact status)

Event type

Event type

Hysteresis

Hysteresis

Close

Open

Close

Hysteresis

Hysteresis

Open

Open

Close

Setpoint

Hysteresis

Hysteresis

Alarm setpoint Setpoint

Hysteresis

Output value

Hysteresis

Output value

PV high-limit

PV low-limit

Deviation

high-imit

Deviation

low-limit

Deviation

high & low

limit

PV

Alarm

setpoint

Alarm

setpoint

Alarm

setpoint

Alarm

setpoint

Deviation
setpoint

Deviation
setpoint

Deviation
setpoint

Deviation within
high & low limits

SP high-limit

SP low- limit

Output high-limit

Output low-limit

PV

SP

SP

SP

PV

PV

PV

Note

If the setup conditions of PV events are not specified using the same conditions also in the

next segment, they are reset at the time the operation of the specified program segment

ends.

With cascade control, you can set PV events to the primary loop and secondary loop.

Switching the Program Pattern Using Contact Inputs

Contact input is applied at [DI001-DI006], [DI101-DI106], and [DI201-DI206] of the
control output terminal block, and [RI001-RI006] on the control DIO expansion terminal
block.
• Before version 3.02

The program pattern is changed using contact inputs of binary representation.

• Version 3.20 and later

In addition to the binary representation, the program pattern can be changed using
contact inputs of binary-coded decimal (BCD) representation. You can select Whether
to use [Binary] or [BCD]. The default setting is [Binary].

1.11 Program Control Related Settings