Par 758, Par 763, Par 765 – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 107: Lue in, Par 762, Par 757, Par 769, Tion is set by, Par 755

Advertising
background image

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

107

Programming and Parameters

Chapter 2

No.

Name
Description

Values

Li

nk

ab

le

Re

ad

-W

ri

te

Da

ta

T

ype

755

Posit Offset Spd

Sets the speed of position offset. A position offset command will not exceed this speed. The actual speed of
offset is limited to a maximum value of 1/(inertia x pos gain) so as not to cause a torque pulse greater than 1 per
unit. The speed will change exponentially.

Default:
Min/Max:
Units:
Scale:

176.4000
-/+14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

756

X Offst SpdFilt

Displays the output of a first order filter whose time response is shaped specifically to provide an output that
represents the actual speed of offset correction. It may be used as a feed forward into speed reference to secure
minimal position error during changes to offset.

Default:
Min/Max:
Units:
Scale:

0.0000
-/+14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

RO Real

757

Abs Posit Offset

Provides an offset to absolute position. Setting

Par 740

[Position Control], bit 8 “Xzero Preset” presets

Par 744

[PositRef EGR Out],

Par 747

[Position Cmmd],

Par 763

[Position Actual] and

Par 765

[Posit Actl Load] with the

value in

Par 762

[Position Fdbk] minus

Par 757

[Abs Posit Offset] upon drive enable.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

758

Pt-Pt Posit Ref

Provides position reference to the point to point position regulator, when the value in

Par 742

[Position Ref Sel]

= 2 “Pt to Pt”. The initial value is latched upon position enable without causing movement. Subsequent changes
to reference are relative to the latched position unless the position is re-referenced by

Par 740

[Position Control],

bit 10 “Pt-Pt ReRef”. Position moves may be made within the limits of plus or minus 31 bits. Point-to-point
reference may be changed, and even reversed, during a move.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

759

Pt-Pt Accel Time

Acceleration time (sec) to base speed, active only in point to point mode. Acceleration to a relatively low speed
may be exponential.

Default:
Min/Max:
Units:

10.0000
0.1000/6553.5000
s

Y

RW Real

760

Pt-Pt Decel Time

Deceleration time (sec) from base speed to zero, active only in point to point mode. Some tailing can be expected
at the end of a move as the drive comes into command position. It is left to the user to select a time that does not
place the drive in current or torque limit. Deceleration from relatively low speed may be exponential.

Default:
Min/Max:
Units:

10.0000
0.1000/6553.5000
s

Y

RW Real

761

Pt-Pt Filt BW

Sets the bandwidth of a low pass filter which affects smoothness at the start of deceleration in the point to point
mode. A high filter bandwidth will produce a more square deceleration torque, one with a higher level of jerk.
Typical values range from 5 to 100 (rad/sec). A zero value will bypass the filter. Tail-out is influenced mainly by

Par 768

[Posit Reg P Gain].

Default:
Min/Max:
Units:

25.0000
0.0000/500.0000
rad/s

Y

RW Real

762 Position

Fdbk

Displays the accumulated pulse count of the selected position feedback. Select a position feedback device with

Par 777

[PositionFdbk Sel].

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

763

Position Actual

Displays the accumulated motor position as a 32-bit integer. It tracks

Par 762

[Position Fdbk]. When the position

regulator is not enabled, this parameter is initialized to Par 762 [Position Fdbk] or to the selected position
reference as determined by

Par 740

[Position Control], bit 6 “AbsPositCtrl”.

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

764

Posit Load Fdbk

Tracks the load position, as a 32-bit integer. When a gear box connects the load to the motor,

Par 766

[Posit FB

EGR Mul] and

Par 767

[Posit FB EGR Div] must be set to account for the gear ratio. Set Par 766 [Posit FB EGR Mul]

equal to Par 767 [Posit FB EGR Div] if the load is directly connected to the motor.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

765

Posit Actl Load

Holds the accumulated output of the Load Gear Ratio as a 32-bit integer and forms the primary feedback for the
position regulator integral channel. It is very important that the load gear ratio be precisely set such that the
delta pulse count of one motor revolution equals the delta pulse count of this parameter. When the position
regulator is not enabled, this parameter is initialized to

Par 762

[Position Fdbk] or to the selected position

reference as determined by

Par 740

[Position Control], bit 6 “AbsPositCtrl”.

Default:
Mi/Max:

0
-/+2147483648

RO 32-bit

Integer

766

Posit FB EGR Mul

A 32-bit integer in the numerator of the load EGR function. It is multiplied by

Par 764

[Posit Load Fdbk] and

divided by

Par 767

[Posit FB EGR Div] to reflect the load pulse count to the motor (effectively removing the gear

box ratio). The accumulated position values

Par 763

[Position Actual] and

Par 765

[Posit Actl Load] will be equal

if the ratio is set properly. There may be some difference due to lost motion in the gear train, but there should
not be an accumulated difference. It is often necessary to count gear teeth as gear box manufacturers often
approximate exact ratios with decimal numbers. Enter a negative value in the numerator to account for reversed
motor rotation.

Default:
Min/Max:

1
-/+1000000

Y

RW 32-bit

Integer

767

Posit FB EGR Div

This is a 32-bit integer that forms the denominator of the load EGR function.

Default:
Min/Max:

1
1/2000000

RW 32-bit

Integer

768

PositReg P Gain

Sets position regulator gain as measured from position error to speed reference. The gain number is identically
equal to position regulator bandwidth in rad/sec. For example: A gain of 10 means that a per unit position error
of 0.1 sec. will effect a 1.0 P.U. speed change (1 per unit position error is the distance traveled in 1 sec. at base
motor speed). The maximum value of this parameter is typically 1/3 of the speed bandwidth (rad/sec) but may
be set considerably higher with careful tuning of the speed regulator output lead/lag filter.

Default:
Min/Max:
Units:

4.0000
0.0000/200.0000
rad/s

Y

RW Real

769

Position Error

Actual position error in motor pulse counts. When the position regulator is not enabled, this 32-bit integer
register is initialized to zero. When the position regulator is enabled, this parameter contains the running value
of position error, often referred to as “following error”.

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

Advertising