Chapter 2

Programming and Parameters

405

Dead Time Comp

The amount of voltage correction used to compensate for the loss of voltage during dead time. Do not adjust.
Contact factory for alternative settings.

Default:
Min/Max:
Units:

0
0/200
%

RW 16-bit

Integer

406

Power Loss Mode

Enter a value to configure the drive's response to a loss of input power, as sensed by an input voltage below the
value specified in

Par 408

[Power Loss Level].

Enter a value of “0” to make the drive fault and coast to a stop (supply no current to the motor) after the

amount of time specified in

Par 407

[Power Loss Time] has expired.

Enter a value of “2” to make the drive fault and continue "normal" operation after the amount of time

specified in Par 407 [Power Loss Time] has expired.

Enter a value of “5” to make the drive provide only motor flux current during the power loss time.

Default:

Options:

0 =

0 =
1 =
2 =

“Coast”

“Coast”

3 = “Reserved”

“Reserved”

4 = “Reserved”

“Continue”

5 = “Flux Only”

407

Power Loss Time

Sets the amount of time that the drive will remain in a ride through condition before a fault is detected.

Default:
Min/Max:
Units:

2.0000
0.0000/60.0000
s

RW Real

408

Power Loss Level

Sets the percentage of the bus voltage at which ride-through begins and modulation ends. When the bus voltage
falls below this level and

Par 406

[Power Loss Mode] is set to 0 “Coast” or 5 “Flux Only”, an alarm (F92 “Ride Thru”)

will be displayed on the HIM and the drive prepares for an automatic restart. Enter a percentage of the bus voltage
derived from the high voltage setting for the voltage class. For example: On a 400-480V drive,

Note: The definition was updated to include the bit settings for parameter 406 for firmware version 4.002.

Default:
Min/Max:
Units:
Scale:

22.1
15/95
%
0

RW 16-bit

Integer

409 Line

Undervolts

Controls the level of bus voltage that is needed to complete precharge and sets the level for undervoltage alarm/
fault detection. Enter a percentage of the bus voltage derived from the value in

Par 401

[Rated Volts].

For example: on a 480V drive,

Default:
Min/Max:
Units:

61.5000
10.0000/90.0000
%

RW Real

410 PreChrg

TimeOut

Sets the time duration of precharge. If bus voltage does not stabilize within this amount of time, a Precharge Error
exception event occurs.

Default:
Min/Max:
Units:

30.0000
10.0000/180.0000
s

RW Real

411 PreChrg

Control

Must equal 1 to allow drive to exit precharge and begin to run. Link this parameter to a controller output word to
coordinate the precharge of multiple drives.

Default:

Options:

1 =

0 =
1 =

“Enbl PrChrg”

“Hold PrChrg”
“Enbl PrChrg”

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

A

0.221 480Vac

2

Ч

Ч

150Vdc

=

0.615 480Vac

2

Ч

Ч

418Vdc

=