Programming and Parameters

Chapter 2

351

Iq Ref Trim

Provides an external source to command, trim or offset the internal motor current reference. This value is summed
with

Par 350

[Iq Actl Ref] before the current limit is applied. Scaling is in per unit motor current.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

Y

RW Real

352

Is Actual Lim

Displays the largest allowable stator motor current. The range of allowable motor current is limited by the
maximum drive current. Scaling is in per unit motor current.

Default:
Min/Max:
Units:

1.0000
0.0000/8.0000
P.U.

RO

Real

353

Iq Actual Lim

Displays the largest allowable torque producing (Iq) motor current. The range of allowable Iq motor current is
limited by the maximum drive current and is adjusted by the motor flux current. Scaling is in per unit Iq motor
current.

Default:
Min/Max:
Units:

1.0000
0.0000/8.0000
P.U.

RO

Real

354

Iq Rate Limit

Enter the maximum rate of change for Current Reference, in per unit current / sec.

Par 90

[Spd Reg BW] will be

limited to 2/3 of this value.

Default:
Min/Max:
Units:

1000.0000
5.0000/10000.0000
/s

Y

RW Real

355

Iq Ref Limited

Displays the current reference output of the rate limiter.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO

Real

356

Mtr Current Lim

Sets the largest allowable motor stator current. The online maximum value of this parameter is

Par 2

[Motor NP

FLA]. The online minimum value is 105% of the current indicated in

Par 488

[Flux Current].

Default:
Min/Max:
Units:

1.5000
0.0000/Calculated
P.U.

Y

RW Real

357

Curr Ref TP Sel

Enter or write a value to select current reference data displayed in

Par 358

[Curr Ref TP Data].

Note: Added values 20…52 for firmware version 3.003. Added value 53 for firmware version 4.001.

Default:

Options:

0 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
15 =
16 =
17 =
18 =
19 =
20 =
21 =
22 =
23 =
24 =
25 =
26 =

“Zero”

“Zero”

27 = “Rated Vds”

“Iq Sum”

28 = “Rated Vqs”

“Iq Lim In”

29 = “RatedLamdVds”

“Iq Lim Out”

30 = “RatedLamdIds”

“Iq Rate Stat”

31 = “RatedLamd ds”

“IqLmOutNoFil”

32 = “RatedLamd qs”

“MtrCrLimStat”

33 = “Iqs”

“Lim'dMtrCrLm”

34 = “Ids”

“Iq Act Limit”

35 = “Vqs”

“Iq Cal Gain”

36 = “Vds”

“Min Lim Stat”

37 = “We”

“Iq Prescale”

38 = “Torque”

“IqtoIs Stat”

39 = “Torque Filtr”

‘Flux Status”

40 = “Lamda Ids”

“Flux LPF Out”

41 = “Lamda Iqs”

“Is Per Unit”

42 = “Lamda Vds”

“Iq Actl +Lim”

43 = “Lamda Vqs”

“Iq Actl -Lim”

44 = “Lamda ds”

“Flx Filt Hld”

45 = “Lamda qs”

“Inverse Flux”

46 = “Lamda ds Flt”

“Impedance P.U.”

47 = “Lamda qs Flt”

“ImpedanceOhm”

48 = “Torque Ref”

“Rated We”

49 = “Iq Reference”

“Leak Induct”

50 = “1/Motor Pole”

“Rated Torque”

51 = “1/Rated Iqs”

“Rated Ids”

52 = “1/Rated Torq”

“Rated Iqs”

53 = “Rs Temp Coef”

358

Curr Ref TP Data

Sets the limit value for the motor torque producing current.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO

Real

359

Motor Flux Est

The Q-axis motor voltage is divided by the motor frequency while field weakening is active. This value is used to
convert the torque command to a motor current (Iqs) command.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO

Real

360

Min Flux

Sets the smallest level of flux used to convert

Par 303

[Motor Torque Ref] to a current reference above base speed.

Note: Changed the minimum value from “0.2500” to “0.1000” for firmware version 4.001.

Default:
Min/Max:
Units:

0.2500
0.1000/1.0000
P.U.

Y

RW Real

361

Flx LpassFilt BW

Sets the bandwidth of the low pass filter that adjusts the response of the flux estimate used in the torque to
current conversion. Since the field time constant varies between motors, a better control response may be
obtained by adjusting the filter time constant. Normally this parameter is not changed unless a significant
disturbance occurs as the motor enters field weakening AND

Par 360

[Min Flux] is less than 1 per unit.

Default:
Min/Max:
Units:

12.0000
0.5000/100.0000
rad/s

Y

RW Real

362

Current Limit Gain

Sets the responsiveness of the current limit. This parameter should not be changed by the user.
Note: This parameter was added for firmware version 2.003.

Default:
Min/Max:

250
0/10000

RW 16-bit

Integer

363

Ki Current Limit

Current Limit Integral gain. This gain is applied to the current limit error signal to eliminate steady state current
limit error. A larger value increases overshoot during a step of motor current/load. This parameter should not be
changed by the user.
Note: This parameter was added for firmware version 2.003.

Default:
Min/Max:

1500
0/10000

RW 16-bit

Integer

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

A

A