Chapter 2

Programming and Parameters

796

Posit Gear Ratio

Sets the load side gear ratio for position control. Adjust this value when the selection of

Par 777

[PositionFdbk

Sel] is not 3 “Motor Fdbk”.
Calculation: Motor Encoder (Rpm) / Load Encoder (Rpm)

Note: This parameter was changed to non-linkable for firmware version 3.001. This parameter was changed to
be linkable for firmware version 3.004.

Default:
Min/Max:

1.00
0.00/9999.00

Y

RW Real

797

BasicIndx Step

Sets the amount added to or subtracted from

Par 799

[BasicIndx Output] on a rising edge of

Par 740

[Position

Control], bit 12 “BscIndx Step”. Note that this value can be positive or negative.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

798

BasicIndx Preset

Sets the value to be moved into

Par 799

[BasicIndx Output] when

Par 740

[Position Control], bit 11 “BscIndx

Enbl” and bit 14 “BscIndx Prst” are both on.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

799

BasicIndx Output

Displays the output of the Position Index function.

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

800

Anlg In1 Data

Displays the scaled final value for Analog Input 1.

Default:
Min/Max:

0.0000
-/+2200000000.0000

RO Real

801

Anlg In1 Value

Displays the actual input value at Analog Input 1. Analog Input 1 may be configured for voltage or current input
signal. For proper selection of the input signal, the DIP switch S-5 and

Par 821

[Analog I/O Units] must be set to

match. Par 801 [Anlg In1 Value] is multiplied by the value in

Par 802

[Anlg In1 Scale] to produce the input to the

lead lag filter function.

Default:
Min/Max:
Units:

0.0000
-/+20.0000
V/mA

RO Real

802

Anlg In1 Scale

Scales the range of Analog Input 1 to the range of

Par 800

[Anlg In1 Data]. Enter the units you want per volt or

mA. For example: If Par 801 [Anlg In1 Value] = 0 - 10V and you enter “6” in this parameter, Par 800 [Anlg In1
Data] will equal 0 - 60V.
Par 801 x Par 802 = Par 800.

Default:
Min/Max:
Units:

0.1000
-/+2200000000.0000
/V or /mA

Y

RW Real

803

Anlg In1 Offset

Applies an offset to Analog Input 1. Use the offset to correct for zero signal errors or to create an offset to the
actual input. The output of the A/D converter is summed with this parameter to produce

Par 801

[Anlg In1

Value].

Default:
Min/Max:
Units:

0.0000
-/+20.0000
V/mA

Y

RW Real

804

AI 1 Filt Gain

Provides the Lead term for the Analog Input 1 filter.

Default:
Min/Max:

1.0000
-/+5.0000

Y

RW Real

805

Anlg In1 Filt BW

Provides the Lag term for the Analog Input 1 filter.

Default:
Min/Max:
Units:

0.0000
0.0000/3760.0000l
rad/s

Y

RW Real

806

Anlg In2 Data

Displays the scaled final value for Analog Input 2.

Default:
Min/Max:

0.0000
-/+2200000000.0000

RO Real

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Type of Input:

Configurable, Voltage or Current

Polarity:

Bi-Polar

Resolution:

14 bit (-8191 to +8191)

DIP Switch

Analog I/O Units

AI 1 Voltage

S5-2 = Open

Par 821 Bit 0 = 0 (False)

AI 1 Current

S5-2 = Closed

Par 821 Bit 0 = 1 (True)

Light

Heavy

Par 804

[Al 1 Filt Gain]

0.25

0.1

Par 805 [Anlg In1 Filt BW]

50

10