Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

109

Programming and Parameters

Chapter 2

783

In Posit Dwell

Position error must be within the value specified by

Par 782

[In Posit BW] for this amount of time before the In

Position detector sets bit 10 “In Position” of

Par 741

[Position Status]. A momentary out-of-position indication

will reset the internal timer and clear the In Position status bit.

Default:
Min/Max:
Units:

0.0040
0.0000/10.0000
s

Y

RW Real

784

Posit Dect1 In

Provides the input variable for Position Watch 1. Position Watch 1 is enabled and configured with

Par 740

[Position Control] bits 16 & 17. Position Watch 1 compares this value with

Par 780

[PositDetct1 Stpt] and sets bit

8 “Posit Watch1” of

Par 741

[Position Status] when the appropriate condition is satisfied. A default link connects

this parameter to

Par 763

[Position Actual].

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

785

Posit Dect2 In

Provides the input variable for Position Watch 2. Position Watch 2 is enabled and configured with

Par 740

[Position Control] bits 18 & 19. Position Watch 2 compares this value with

Par 781

[PositDetct2 Stpt] and sets bit

9 “Posit Watch2” of

Par 741

[Position Status] when the appropriate condition is satisfied. A default link connects

this parameter to

Par 763

[Position Actual].

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

786

Xsync Status

Bit 0 “Sync Pulse” will go high for 0.5ms latching the Sync Generator inputs to the Sync Generator outputs. The period at which this bit is set is determined by

Par 787

[Xsync Gen Period].

Note: Bit 1 was changed to “Reserved” for firmware version 2.004.

787

Xsync Gen Period

Sets the period for the Sync Pulse Generator. Bit 0 of

Par 786

[Xsync Status] will be set for 0.5 msec and will be

cleared for 0.5msec x 2[Xsync Gen Period] - 0.5 msec.
Note: Values 5 - “16 msec” and 6 - “32 msec” were added for firmware version 2.004.

Default:

Options:

1 =

0 =
1 =
2 =
3 =

“1 msec”

“0.5 msec”

4 = “8 msec”

“1 msec”

5 = “16 msec”

“2 msec”

6 = “32 msec”

“4 msec”

788

Xsync In 1

32-bit integer input of the Sync Generator. Latched to

Par 789

[Xsync Out 1]. Link any 32-bit integer parameter to

this input parameter.
Note: This parameter was changed to an unsigned integer data type and linkable to parameters that are either
real or integer values for firmware version 4.001.

Default:
Min/Max:

0
0/4294967295

Y

RW 32-bit

Integer

789

Xsync Out 1

Sync Generator 32-bit output register. Latched to

Par 788

[Xsync In 1] every time bit 0 “Sync Pulse” of Par 786

[Xsync Status] is set.
Note: This parameter was changed to an unsigned integer data type and linkable to parameters that are either
real or integer values for firmware version 4.001.

Default:
Min/Max:

0
0/4294967295

RO 32-bit

Integer

790

Xsync In 2

32-bit integer input of the Sync Generator. Latched to

Par 791

[Xsync Out 2]. Link any 32-bit integer parameter to

this input parameter.
Note: This parameter was changed to an unsigned integer data type and linkable to parameters that are either
real or integer values for firmware version 4.001.

Default:
Min/Max:

0
0/4294967295

Y

RW 32-bit

Integer

791

Xsync Out 2

Sync Generator 32-bit output register. Latched to

Par 790

[Xsync In 2] every time bit 0 “Sync Pulse” of

Par 786

[Xsync Status] is set.
Note: This parameter was changed to an unsigned integer data type and linkable to parameters that are either
real or integer values for firmware version 4.001.

Default:
Min/Max:

0
0/4294967295

RO 32-bit

Integer

792

Xsync Out 2 Dly

Displays data of

Par 791

[Xsync Out 2] from the last sync period.

Note: This parameter was changed to an unsigned integer data type and linkable to parameters that are either
real or integer values for firmware version 4.001.

Default:
Min/Max:

0
0/4294967295

RO 32-bit

Integer

793

Xsync In 3

32-bit integer input of the Sync Generator. Latched to

Par 794

[Xsync Out 3]. Link any 32-bit integer parameter to

this input parameter.
Note: This parameter was changed to an unsigned integer data type and linkable to parameters that are either
real or integer values for firmware version 4.001.

Default:
Min/Max:

0
0/4294967295

Y

RW 32-bit

Integer

794

Xsync Out 3

Sync Generator 32-bit output register. Latched to

Par 793

[Xsync In 3] every time bit 0 “Sync Pulse” of

Par 786

[Xsync Status] is set.
Note: This parameter was changed to an unsigned integer data type and linkable to parameters that are either
real or integer values for firmware version 4.001.

Default:
Min/Max:

0
0/4294967295

Y

RW 32-bit

Integer

795

Xsync Out 3 Dly

Displays data of

Par 794

[Xsync Out 3] from the last sync period.

Note: This parameter was changed to an unsigned integer data type and linkable to parameters that are either
real or integer values for firmware version 4.001.

Default:
Min/Max:

0
0/4294967295

Y

RW 32-bit

Integer

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Sy

nc

U

nst

bl

Sy

nc

L

oss

In

te

rpInS

ync

Re

se

rv

ed

Sy

nc

Pu

ls

e

Default

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

0

0

0

x

0

Bit

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True

Advertising