831

Anlg Out1 Sel

Identifies the signal used on Analog Output 1. If the desired signal is not available in the selection list, choose
option 0 - “User Select” and link with

Par 832

[Anlg Out1 DInt] or

Par 833

[Anlg Out1 Real] to select the desired

parameter for output.

The following table provides the parameter that corresponds to the option selected in this parameter.

Default:

Options:

17 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =

“Speed Fdbk”

“User Select”

14 = “Reserved”

“Output Freq”

15 = “Motor TrqRef”

“Sel Spd Ref”

16 = “MtrTrqCurRef”

“Output Curr”

17 = “Speed Ref”

“Trq Cur (Iq)”

18 = “Speed Fdbk”

“% Motor Flux”

19 = “Torque Est”

“Output Power”

20 = “Scl Spd Fdbk”

“Output Volts”

21 = “RampedSpdRef”

“DC Bus Volts”

22 = “Spd Reg Out”

“PI Reference”

23 = “MOP Level”

“PI Feedback”

24 = “Trend 1 DInt”

“PI Error”

25 = “Trend 1 Real”

“PI Output”

26 = “Trend 2 DInt”

“Reserved”

27 = “Trend 2 Real”

832

Anlg Out1 DInt

Link this parameter to an integer source parameter that will control Analog Output 1.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

833

Anlg Out1 Real

Link this parameter to a real (floating point) source parameter that will control Analog Output 1.

Default:
Min/Max:

0.0000
-/+2200000000.0000.0000

Y

RW Real

834

Anlg Out1 Offset

Provides an offset for Analog Output 1 before the scaling and limit blocks in the Analog Output 1 function. This
parameter value is summed with either

Par 832

[Anlg Out1 DInt] or

Par 833

[Anlg Out1 Real] at the beginning of

the function.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

835

Anlg Out1 Scale

Scales the range of the source parameter to the range of Analog Output 1. For example: If

Par 831

[Anlg Out1 Sel]

is set to 1 “Output Freq”, the output frequency of the drive is 0 - 60Hz and you enter “6” in this parameter,

Par 837

[Anlg Out1 Value] = 6Hz per 1V, or 0 - 60Hz.

Par 832

[Anlg Out1 DInt] or

Par 833

[Anlg Out1 Real] is multiplied by this number after the limit function.

Note: The turn-off point for this parameter has been changed from ±0.001 to ±0.0001 for firmware version
4.002.

Default:
Min/Max:
Units:

0.0000
-/+2200000000.0000
/V

Y

RW Real

836

Anlg Out1 Zero

Applies an offset to the scaled value of Analog Output 1. This parameter is summed with the output of the
scaling block. This sum produces

Par 837

[Anlg Out1 Value]. Typically this value corresponds to 0V for Analog

Output 1.

Default:
Min/Max:
Units:

0.0000
-/+20.0000
V

Y

RW Real

837

Anlg Out1 Value

Displays the voltage reference for Analog Output 1 before the digital to analog conversion.

Default:
Min/Max:
Units:

0.0000
-/+10.0000
V

RO Real

838

Anlg Out2 Sel

Identifies the signal used on Analog Output 2. If the desired signal is not available in the selection list, choose
option 0 - “User Select” and link with

Par 839

[Anlg Out2 DInt] or

Par 840

[Anlg Out2 Real] to select the desired

parameter for output. Refer to

Par 831

for a list of parameters that correspond to the option selected in this

parameter.

Default:

Options:

3 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =

“Output Curr”

“User Select”

14 = “Reserved”

“Output Freq”

15 = “Motor TrqRef”

“Sel Spd Ref”

16 = “MtrTrqCurRef”

“Output Curr”

17 = “Speed Ref”

“Trq Cur (Iq)”

18 = “Speed Fdbk”

“% Motor Flux”

19 = “Torque Est”

“Output Power”

20 = “Scl Spd Fdbk”

“Output Volts”

21 = “RampedSpdRef”

“DC Bus Volts”

22 = “Spd Reg Out”

“PI Reference”

23 = “MOP Level”

“PI Feedback”

24 = “Trend 1 DInt”

“PI Error”

25 = “Trend 1 Real”

“PI Output”

26 = “Trend 2 DInt”

“Reserved”

27 = “Trend 2 Real”

839

Anlg Out2 DInt

Link this parameter to an integer source parameter that will control Analog Output 2.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

840

Anlg Out2 Real

Link this parameter to a real (floating point) source parameter that will control Analog Output 2.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Option

Parameter

Option

Parameter

1 “Output Freq”

310

[Output Freq]

16 “MtrTrqCurRef”

305

[Mtr Trq Curr Ref]

2 “Sel Spd Ref”

40

[Selected Spd Ref]

17 “Speed Ref”

301

[Motor Speed Ref]

3 “Output Curr”

308

[Output Current]

18 “Speed Fdbk”

71

[Filtered SpdFdbk]

4 “Trq Cur (Iq)”

499

[Trq Cur Fdbk (Iq)]

19 “Torque Est”

471

[Estimated Torque]

5 “% Motor Flux”

309

[% Motor Flux]

20 “Scl Spd Fdbk”

72

[Scaled Spd Fdbk]

6 “Output Power”

311

[Output Power]

21 “RampedSpdRef”

43

[Ramped Spd Ref]

7 “Output Volts”

307

[Output Voltage]

22 “Spd Reg Out”

101

[SpdReg Integ Out]

8 “DC Bus Volts”

306

[DC Bus Voltage]

23 “MOP Level”

1090

[MOP Level Real]

9 “PI Reference”

181

[PI Reference]

24 “Trend 1 DInt”

572

[Trend Out1 DInt]

10 “PI Feedback”

182

[PI Feedback]

25 “Trend 1 Real”

573

[Trend Out1 Real]

11 “PI Error”

183

[PI Error]

26 “Trend 2 DInt”

576

[Trend Out2 DInt]

12 “PI Output”

180

[PI Output]

27 “Trend 2 Real”

577

[Trend Out2 Real]

15 “Motor TrqRef”

303

[Motor Torque Ref]