Safe-off terminal descriptions, Wiring example, Safe-off terminal descriptions wiring example – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual
Page 207

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013
207
ATEX Approved PowerFlex 700S, Phase II Drives in Group II Category (2) Applications with ATEX Approved Motors
Appendix E
Safe-Off Terminal Descriptions
Wiring Example
No. Signal
Description
1
+24V DC
Connections for power to energize coil.
33.3 mA typical, 55 mA maximum.
2
24V Common
3
Monitor - N.C.
Normally closed contacts for monitoring relay
status.
Maximum Resistive Load:
250V AC / 30V DC / 50 VA / 60 Watts
Maximum Inductive Load:
250V AC / 30V DC / 25 VA / 30 Watts
4
Common - N.C.
1 2 3 4 5 6 7 8 9 10
13
12
11
1 2 3 4 5 6
24V DC Common
PowerFlex 700S
Phase II AC Drive
+24V DC
1
2
13
16
3
4
1
2
Safe Off Option
AC Line
Input Power
Digital In 6 (Enable)
Digital In 4-6 Com.
M
Gate Control
Power Supply
Gate Control
Circuit
Motor
Over Temperature
Sensor(s)