Safe-off terminal descriptions, Wiring example, Safe-off terminal descriptions wiring example – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 207

Advertising
background image

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

207

ATEX Approved PowerFlex 700S, Phase II Drives in Group II Category (2) Applications with ATEX Approved Motors

Appendix E

Safe-Off Terminal Descriptions

Wiring Example

No. Signal

Description

1

+24V DC

Connections for power to energize coil.
33.3 mA typical, 55 mA maximum.

2

24V Common

3

Monitor - N.C.

Normally closed contacts for monitoring relay
status.
Maximum Resistive Load:
250V AC / 30V DC / 50 VA / 60 Watts
Maximum Inductive Load:
250V AC / 30V DC / 25 VA / 30 Watts

4

Common - N.C.

1 2 3 4 5 6 7 8 9 10

13

12

11

1 2 3 4 5 6

24V DC Common

PowerFlex 700S

Phase II AC Drive

+24V DC

1

2

13

16

3

4

1

2

Safe Off Option

AC Line

Input Power

Digital In 6 (Enable)

Digital In 4-6 Com.

M

Gate Control

Power Supply

Gate Control

Circuit

Motor

Over Temperature

Sensor(s)