Chapter 2

Programming and Parameters

202

Time Axis Rate

Sets rate (1/sec) for the Time Function Generator to ramp from an output of 0 to 1 and from 1 to 0.

Default:
Min/Max:
Units:

1.0000
0.0100/20.0000
/s

Y

RW Real

203

Time Axis Output

The output of the Time Function Generator. When the Time Function Generator is enabled by

Par 151

[Logic

Command] bit 3 “Time Axis En”, or

Par 153

[Control Options], bit 24 “Time Axis En”, the value of this parameter

ramps from 0 to 1 at a rate determined by

Par 202

[Time Axis Rate]. Conversely, when the Time Function Generator

is disabled, the value of this parameter ramps from 1 to 0.

Default:
Min/Max:

0.0000
0.0000/1.0000

RO

Real

204

LimGen Y axis Mx

Sets

Par 207

[Limit Gen Hi Out] and

Par 208

[Limit Gen Lo Out] when the absolute value of

Par 206

[LimGen X axis

In] is greater than or equal to 1.

Default:
Min/Max:
Units:

0.2500
0.0000/8.0000
P.U.

Y

RW Real

205

LimGen Y axis Mn

Sets

Par 207

[Limit Gen Hi Out] and

Par 208

[Limit Gen Lo Out] when the absolute value of

Par 206

[LimGen X axis

In] is equal to 0.

Default:
Min/Max:
Units:

0.0500
0.0000/8.0000
P.U.

Y

RW Real

206

LimGen X axis In

The X axis input to the Limit Generator. Typically this parameter is linked to a speed reference or to

Par 203

[Time

Axis Output].

Default:
Min/Max:

Y

Y

Y

RW Real

207

Limit Gen Hi Out

Displays the positive output of the Limit Generator. When

Par 206

[Limit Gen X axis In] is greater than or equal to

1, this value equals

Par 204

[Limit Gen Y axis Mx]. When Par 206 [Limit Gen X axis In] is equal to 0, this value

equals

Par 205

[Limit Gen Y axis Mn]. For values of X Axis input between 0 and 1, the value of this parameter is

interpolated from Y axis min. and max. values. Typically it is linked to

Par 188

[PI Integ HLim].

Default:
Min/Max:
Units:

8.0000
0.0000/8.0000
P.U.

RO

Real

208

Limit Gen Lo Out

Displays the negative output of the Limit Generator. The value of this parameter is the negative of

Par 207

[Limit

Gen Hi Out]. Typically it is linked to

Par 189

[PI Integ LLim].

Default:
Min/Max:
Units:

-8.0000
-8.0000/0.0000
P.U.

RO

Real

210

PeakDtct Ctrl In

Sets the configuration of the two peak/level detectors. Peak detection (when “set” and “hold” are off) causes the output to capture the peak min./max.
• Bit 2 “Peak1SelHigh” and bit 6 “Peak2SelHigh” determine if the peak/level detector is positive or negative. If the bit is set the detector detects positive peaks or levels above the preset. If the bit

is not set the detector detects "valleys" or levels below the preset. The output shows the min. or max. peak.

• Bit 0 “Peak 1 Set” bit is used to reset the output to the value in

Par 214

[PeakDtct1 Preset] (default 0). Bit 4 “Peak 2 Set” bit is used to reset the output to the value in

Par 218

[PeakDtct2 Preset]

(default 0).

• Bit 1“Peak 1 Hold” is used to hold the output at the present value in Par 214 [PeakDtct1 Preset]. Bit 5 “Peak 2 Hold” is used to hold the output at the present value in Par 218 [PeakDtct2 Preset].

211

PeakDtct Status

Status of peak/level detectors. A peak detector sets its “Change” bit for one scan when it detects a peak. The” Change” bit is off when set or when the “Hold” bit is on.

212

PkDtct1 In DInt

Integer input to the first peak/level detector.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

213

PkDtct1 In Real

Floating point input to the first peak/level detector.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

214

PeakDtct1 Preset

The first detector (in set or hold modes) compares this value to its input for level detection. When the detector
trips (in set mode) it transfers the value of this parameter to its output.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

215

PeakDetect1 Out

Output from the first peak/level detector.

Default:
Min/Max:

0.0000
-/+2200000000.0000

RO

Real

216

PkDtct2 In DInt

Integer input to second peak/level detector.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

217

PkDtct2 In Real

Floating point input to second peak/level detector.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

218

PeakDtct2 Preset

The second detector (in set or hold modes) compares this value to its input for level detection. When the detector
trips (in set mode) it transfers the value of this parameter to its output.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Pe

ak

2S

el

H

ig

h

Pe

ak

2

H

ol

d

Pe

ak

2

S

et

Re

se

rv

ed

Pe

ak

1S

el

H

ig

h

Pe

ak

1

H

ol

d

Pe

ak

1

S

et

Default

x

x

x

x

x

x

x

x

x

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Pe

ak 2 C

hng

Pe

ak 1 C

hng

Default

x

x

x

x

x

x

x

x

x

x

x

x

x

x

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True