Drive status indicators, E drive status indicators – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 140

Advertising
background image

140

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Chapter 3

Troubleshooting

Drive Status Indicators

Table 3 - Drive Status Indicator Descriptions

1

2

3

#

Name

Color

State

Description

DR

IV

E

Po

w

er S

truc

ture

1

PWR (Power)

Green

Steady

Illuminates when power is applied to the drive.

2

STS
(Status)

Green

Flashing

Drive ready, but not running & no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing

When running, a type 2 (non-configurable) alarm condition exists, drive continues to run. When
stopped, a start inhibit exists and the drive cannot be started.

Steady

A type 1 (user configurable) alarm condition exists, but drive continues to run.

Red

Flashing

A fault has occurred.

Steady

A non-resettable fault has occurred.

Red /
Yellow

Flashing
Alternately

The drive is in flash recovery mode. The only operation permitted is flash upgrade.

Co

nt

ro

l A

sse

mbly

Co

mmunic

at

io

ns 3

PORT

Refer to the
Communication Adapter
User Manual

Status of DPI port internal communications (if present).

MOD

Status of communications module (when installed).

NET A

Status of network (if connected).

NET B

Status of secondary network (if connected).

Co

nt

ro

l

(1)

SYNCHLINK

Green

Steady

The module is configured as the time keeper.
or
The module is configured as a follower and synchronization is complete.

Green

Flashing

The follower(s) are not synchronized with the time keeper.

Red

Flashing

The module is configured as a time master on SynchLink and has received time information from
another time master on SynchLink.

ENABLE

Green

On

The drive’s enable input is high.

Green

Off

The drive’s enable input is low.

(1) SynchLink LEDs are located on the SynchLink daughtercard on the main circuit board in the control cassette. Refer to the SynchLink System Design Guide, publication 1756-TD008, for

more information.