Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

85

Programming and Parameters

Chapter 2

468

MC TP1 Bit

Displays the data selected by

Par 466

[MC TP1 Select]. This display should only be used if the selected value is

bit-enumerated data. Par 468 [MC TP1 Bit] is a diagnostic tool you can use to view internal drive parameters.

Default:
Min:
Max:

00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111

RO

32-bit
Boolean

469 FVC

CEMF

Comp

Displays the current regulator feedforward compensation. Do not change this value.

Default:
Min/Max:
Units:

0
0/100
%

RW 16-bit

Integer

470

Flux Reg P Gain2

Displays the additional proportional gain used at the start of Bus voltage limited field weakening. Do not
change this value.

Default:
Min/Max:

1000
0/32767

RW 16-bit

Integer

471

Estimated Torque

Displays the calculated motor shaft torque.
Notes: This parameter was added for firmware version 2.003. The Units and Scale information were added for
firmware version 4.002.

Default:
Min/Max:
Units:
Scale:

0.0
+/-8.0 P.U.
P.U.
1.0 = 100% of the Motor Torque

RO

Real

472 PreCharge

Delay

Adjusts the delay between the time all other precharge conditions have been met and the time the drive
leaves the precharge state. Can be used to control the sequence of precharge completion in a drive system.
The maximum value of this parameter is calculated as follows:
Par 472 [PreCharge Delay] =

Par 410

[PreChrg TimeOut] - 1.0 second.

Default:
Min/Max:
Units:

2.0
0.0/Calculated
s

RW 16-bit

Integer

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

A

A

A