Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

39

Programming and Parameters

Chapter 2

107

Slip RPM Meter

Displays the present amount of adjustment being applied as slip compensation.
Note: This parameter was added for firmware version 2.003.

Default:
Min/Max:
Units:

0.0
+/- 3000.0
rpm

RO 16-bit

Integer

108

Spd Reg TP Sel

Enter or write a value to select Speed Regulator data displayed in

Par 109

[Spd Reg TP Data].

Note: The values for options 10 & 11 were changed to “Reserved” for firmware version 2.004.

Default:

Options:

0 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
15 =
16 =
17 =
18 =
19 =
20 =
21 =
22 =
23 =
24 =
25 =
26 =

“Zero”

“Zero”

27 = “Spd FiltOut”

“Iq Rate BW”

28 = “Servo Lock”

“Reserved”

29 = “Spd+ServLock”

“PGain Max BW”

30 = “Prop Output”

“BW Limit”

31 = “Intg Input”

“InertiaMaxBW”

32 = “Scld Int Pre”

“BW Lim Stat”

33 = “Sel Int Pre”

“BW Select”

34 = “Droop Output”

“Totl Inertia”

35 = “Out Lim Stat”

“TI Lim Stat”

36 = “Intg Hold”

“Reserved”

37 = “Srlss ZeroWe”

“Reserved”

38 = “I GainParLim”

“I Rate Limit”

39 = “P GainParLim”

“I RtLim Stat”

40 = “SrvLck ParLm”

“PGain Max”

41 = “AntiBkup PLm”

“GnMx LimStat”

42 = “Droop ParLim”

“Damping”

43 = “Pos Lim Stat”

“Dmp Lim Stat”

44 = “Neg Lim Stat”

“Reserved”

45 = “Limiter Out”

“Srls KpMxBW”

46 = “Active Pgain”

“Srls BWLimit”

47 = “Active Igain”

“SrlsInrtMxBW”

48 = “Reserved”

“SrlsBWSelect”

49 = “Reserved”

“Srls BW Calc”

50 = “Reserved’

“Snsr BW Calc”

51 = “Reserved”

“Reserved”

52 = “Reserved”

“Reserved”

53 = “Reserved”

109

Spd Reg TP Data

Displays the data selected by

Par 108

[Spd Reg TP Sel].

Default:

Min/Max:
Units:

0.0000

-/+8.0000 P.U.
P.U.

RO Real

110

Speed/TorqueMode

Selects the source for the drive torque reference.
Note: Values 7 & 8 were added for firmware version 3.001.

Default:

Options:

1 =

0 =
1 =
2 =
3 =
4 =

“Speed Reg”

“Zero Torque”

5 = “Sum Spd/Trq”

“Speed Reg”

6 = “AbsMnSpd/Trq”

“Torque Ref”

7 = “SLAT Minimum”

“Min Spd/Trq”

8 = “SLAT Maximum”

“Max Spd/Trq”

111

Torque Ref 1

Supplies an external motor torque reference to the drive. This parameter is divided by the value in

Par 112

[Torq Ref1 Div]. A value of 1.0 represents rated torque of the motor.

Default:
Min/Max:
Scale:

0.0000
-/+2200000000.0000
1.0 Rated Motor Torque

Y

RW Real

112

Torque Ref1 Div

Par 111

[Torque Ref 1] is divided by this number. Use this parameter to scale the value of Par 111 [Torque Ref 1].

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

113

Torque Ref 2

Supplies an external motor torque reference to the drive. This parameter is multiplied by the value in

Par 114

[Torq Ref2 Mult]. A value of 1.0 represents rated torque of the motor.

Default:
Min/Max:
Scale:

0.0000
-/+2200000000.0000
1.0 Rated Motor Torque

Y

RW Real

114

Torque Ref2 Mult

Par 113

[Torque Ref 2] is multiplied by this number. Use this parameter to scale the value of Par 113 [Torque Ref

2].

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

115

Torque Trim

The amount added to

Par 111

[Torque Ref 1] and

Par 113

[Torque Ref 2] before the Speed/Torque Mode Selector.

A value of 1.0 represents rated torque of the motor.

Default:
Min/Max:
Units:
Scale:

0.0000
-/+8.0000 P.U.
P.U.
1.0 Rated Motor Torque

Y

RW Real

116

Torque Step

The amount added to the selected Torque Reference before notch filtering or limits are applied. A value of 1.0
represents rated torque of the motor.

Default:
Min/Max:
Units:
Scale:

0.0000
-/+8.0000 P.U.
P.U.
1.0 Rated Motor Torque

Y

RW Real

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e