Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

15

Drive Start-Up

Chapter 1

Start Up the Drive

6.

Press Enter (

) on the HIM.

The Assisted Start routine will prompt you for the required information
needed to start-up the drive and complete the autotuning procedures. See

Figure 1

on page

16

for a flow chart of the Assisted Start routine.

Note:

When starting up some high impedance motor applications, the

“Power Circuit Test” may fail. If this test fails, the HIM displays the
following fault description text:

Power Circuit Diagnostic Test Detected Error: XX_XX no gate, open
circuit, bad I sensor, press Enter.

If this failure occurs, do the following:

Verify the connections between the motor and the drive; make sure that
a disconnect device or contactor is not interfering with the signal.

Press Enter to continue and perform the Direction Test. If the
Direction Test is successful, continue with the Start-Up routine -
ignoring the failure. If the Direction Test fails, check for an open
connection or bad current sensor.

7.

When the Assisted Start routine is finished and Done/Exit displays on the

HIM, press Enter (

) to save any changed and/or updated data.

IMPORTANT

Always exit the Assisted Start routine before cycling power to the drive.