Par 852 – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 116

Advertising
background image

116

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Chapter 2

Programming and Parameters

852

Dig Out 2 Bit

Selects the bit, from the word linked to

Par 851

[Dig Out 2 Data], that will change the status of Digital Output 2

(e.g., when

Par 852

[Dig Out 2 Bit] equals 0, bit 0 of Par 851 [Dig Out 2 Data] will control Digital Output 2).

Default:
Min/Max:

0
-32/31

Y

RW 16-bit

Integer

853

Dig Out2 On Time

Defines the amount of time between a False to True transition on the output status and the corresponding
change in state of Digital Output 2. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or digital output will not change state. Par 853 [Dig Out2 On Time]
can be disabled by setting the delay time to 0 (zero).
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:
Units:

0.00
0.00/600.00
s

RW 16-bit

Integer

854

Dig Out2 OffTime

Defines the amount of time between a True to False transition on the output status and the corresponding
change in state of Digital Output 2. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or digital output will not change state.
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:
Units:

0.0
0.0/600.00
s

RW 16-bit

Integer

855

Rly Out3 Sel

Identifies the signal used on Digital Output 3. If the desired signal is not available in the selection list, choose
option 0 - “User Select” and link with

Par 856

[Rly Out3 Data] and

Par 857

[Rly Out3 Bit] to select the desired

parameter for output.

Default:

Options:

1 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =

“Not Fault”

“User Select”

15 = “Torque Limit”

“Not Fault”

16 = “Power Limit”

“Not Alarm”

17 = “Fault”

“Ready”

18 = “Alarm”

“Running”

19 = “Command Dir”

“Reserved”

20 = “Actual Dir”

“Reserved”

21 = “Jogging”

“Enable On”

22 = “In Position”

“Active”

23 = “Posit Watch1”

“At Speed”

24 = “Posit Watch2”

“At Setpt 1”

25 = “Cmpr 1 A</=B”

“Above Setpt 2”

26 = “Cmpr 1 A>/=B”

“At ZeroSpeed”

27 = “Cmpr 2 A</=B”

“Speed Limit”

28 = “Cmpr 2 A>/=B”

“CurrentLimit”

856

Rly Out3 Data

Link a word to this parameter that will control the Relay Output 3. The bit within the selected word that will
control Relay Output 3 is set by

Par 857

[Rly Out3 Bit].

Default:
Min:
Max:

00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111

Y

RW 32-bit

Boolean

857

Rly Out3 Bit

Selects the bit, from the word linked to

Par 856

[Rly Out3 Data] that will change the status of the Relay Output 3

(e.g., when Par 857 [Rly Out3 Bit] equals 0, bit 0 of Par 856 [Rly Out3 Data] will control the Relay Output 3).

Default:
Min/Max:

0
-32/31

Y

RW 16-bit

Integer

858

Rly Out3 On Time

Defines the amount of time between a False to True transition on the output status and the corresponding
change in state of Relay Output 3. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or relay output will not change state. Par 858 [Rly Out3 On Time]
can be disabled by setting the delay time to 0 (zero).
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:
Units:

0.00
0.00/600.00
s

RW 16-bit

Integer

859

Rly Out3 OffTime

Defines the amount of time between a True to False transition on the output status and the corresponding
change in state of Relay Output 3. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or relay output will not change state.
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:
Units:

0.00
0.00/600.00
s

RW 16-bit

Integer

General BitSwap Description

The six (6) Bit Swap functions are used to replace one bit in a word with one bit from a different word. This is typically done to a control word where one bit in the control word
is replaced by a bit from another word such as a digital input. Four (4) input parameters and one (1) output parameter are used to accomplish each Bit Swap function. Refer to
the User Functions 1 block diagram on

page 192

.

860

865

870

875

880

885

BitSwap 1A Data

BitSwap 2A Data

BitSwap 3A Data

BitSwap 4A Data

BitSwap 5A Data

BitSwap 6A Data

This is the main word in which 1 bit will be edited. All of the data from this word except the selected bit in

Par

861

[BitSwap 1A Bit] are passed to

Par 864

[BitSwap 1 Result].

Default:
Min/Max:

0
32 bits of data

Y

RW 32-bit

Boolean

861

866

871

876

881

886

BitSwap 1A Bit

BitSwap 2A Bit

BitSwap 3A Bit

BitSwap 4A Bit

BitSwap 5A Bit

BitSwap 6A Bit

This parameter specifies the bit to be replaced in

Par 860

[BitSwap 1A Data].

Default:
Min/Max:

0
0/31

RW 16-bit

Integer

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e