Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

143

Troubleshooting

Chapter 3

Precharge Board Status Indicators

The Precharge Board indicators (LEDs) are found on Frame 5 & 6 drives only
and are located above the “Line Type” Phase selection jumper. Refer to the
PowerFlex 700S Adjustable Frequency Drive - Phase II Control, Frames 1…6
Installation Instructions, publication

20D-IN024

, for the location of the Phase

selection jumper.

Name

Color

State

Description

Power

Green

Steady

Indicates when precharge board power supply is operational

Alarm

Yellow

Flashing
[1]
[2]
[3]
[4]
[5]
[6]
[7]

Number in “[ ]” indicates flashes and associated alarm

(1)

:

Low line voltage (<90%).
Very low line voltage (<50%).
Low phase (one phase <80% of line voltage).
Frequency out of range or asymmetry (line sync failed).
Low DC bus voltage (triggers ride-through operation).
Input frequency momentarily out of range (40-65 Hz).
DC bus short circuit detection active.

(1) An alarm condition automatically resets when the condition no longer exists

Fault

Red

Flashing
[2]
[4]

Number in “[ ]” indicates flashes and associated fault

(2)

:

DC bus short (Udc <2% after 20 ms).
Line sync failed or low line (Uac <50% Unom).

(2) A fault indicates a malfunction that must be corrected and can only be reset after cycling power.