Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

125

Programming and Parameters

Chapter 2

1099

AddSub 1 Result

This is the result output from the Add and Subtract function. See

Par 1096

.

Equation:

Par 1099

= (

Par 1096

+

Par 1097

) -

Par 1098

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

RO Real

1100

AddSub 2 Input

Input value to be added to and/or subtracted from as need with the Add and Subtract function. This input will be
added with

Par 1101

[AddSub 2 Add]. The result will be subtracted from by the value in

Par 1102

[AddSub 2

Subtrct]. The result of the operation is loaded to

Par 1103

[AddSub 2 Result].

Equation: Par (1100 + Par 1101) - Par 1102 = Par 1103

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

1101

AddSub 2 Add

This value is added to the value of

Par 1100

[AddSub 2 Input]. The result will be subtracted from by

Par 1102

and

loaded into

Par 1103

. See Par 1100.

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

1102

AddSub 2 Subtrct

This value is subtracted from the result of

Par 1100

+

Par 1101

. The result will be loaded into

Par 1103

. See Par

1100.
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

1103

AddSub 2 Result

This is the result output from the Add and Subtract function. See

Par 1100

.

Equation:

Par 1103

= (

Par 1100

+

Par 1101

) -

Par 1102

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

RO Real

1104

AddSub 3 Input

Input value to be added to and/or subtracted from as need with the Add and Subtract function. This input will be
added with

Par 1105

[AddSub 3 Add]. The result will be subtracted from by the value in

Par 1106

[AddSub 3

Subtrct]. The result of the operation is loaded to

Par 1107

[AddSub 3 Result].

Equation: Par (1104 + Par 1105) - Par 1106 = Par 1107

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

1105

AddSub 3 Add

This value is added to the value of

Par 1104

[AddSub 3 Input]. The result will be subtracted from by

Par 1106

and

loaded into

Par 1107

. See Par 1104.

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

1106

AddSub 3 Subtrct

This value is subtracted from the result of

Par 1104

+

Par 1105

. The result will be loaded into

Par 1107

. See Par

1104

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

1107

AddSub 3 Result

This is the result output from the Add and Subtract function. See Par 1104.

Equation:

Par 1107

= (

Par 1104

+

Par 1105

) -

Par 1106

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

1.0000
-/+2200000000.0000

RO Real

1108

DelTmr1 TrigData

Link a word to this parameter that will control a user-defined on or off delay timer. The bit within the selected
word that will control the delay timer is set by

Par 1109

[DelTmr1 Trig Bit]. The user-defined on/off delay timer is

enabled by setting bit 6 “Delay Timer” of

Par 1000

[UserFunct Enable].

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

0
32 bits of data

Y

RW 32-bit

Boolean

1109

DelTmr1 Trig Bit

Selects the bit, from the word linked to

Par 1108

[DelTmr1 TrigData], that will change the status of the user-

defined delay timer to on or off. When Par 1109 [DelTmr1 Trig Bit] is a positive number, the delay timer is an “on”
timer. When Par 1109 is a negative number, the delay timer is an “off” timer.
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:

0
-/+32

RW 16-bit

Integer

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Delay

Timer 1

1108

1112

00

DelayTimer 1 Data

1110

DelayTimer 1PrSet

1111

DelayTimer 1Stats

DelayTimer 1Accum

1109

DelayTimer 1 Bit

00

00

Enabled

Timing

Done