Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 40

Advertising
background image

40

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Chapter 2

Programming and Parameters

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

117

NotchAttenuation

Sets the depth for the Notch Filter. Attenuation is the ratio of the output to the input at the notch frequency. An
attenuation of 30 means that the notch output is 1/30

th

of the input at the specified frequency.

Calculation: Attenuation = Input / Output

Default:
Min/Max:

50
0/500

Y

RW Real

118

Notch Filt Freq

The center frequency for Notch filter. To disable, set to zero (0).

Default:
Min/Max:
Units:

0.0000
0.0000/500.0000
Hz

Y

RW Real

119 SLAT

ErrorSetpnt

Determines the rpms at which the drive will switch from speed mode to the Speed Limited Adjustable Torque
(SLAT) min. or SLAT max. mode, identified in

Par 110

[Speed/Torque Mode] bit 7 “SLAT Minimum” or bit 8 “SLAT

Maximum”.
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:
Units:

0.005
0.0/0.1
rpm

Y

RW Real

120 SLAT

Dwell

Time

SLAT control dwell time. The time in seconds that the drive can be above the error set point in

Par 119

[SLAT ErrorSetpnt] before returning to the SLAT min. or SLAT max. mode.

Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:
Units:

0.0
0.0/2.0
s

Y

RW Real

123

Trq PosLim Actl

Sets the internal torque limit for positive torque reference values. The positive internal motor torque will not be
allowed to exceed this value.

Default:
Min/Max:
Units:

1.0
0.0/8.0
P.U.

RO

Real

124

Trq NegLim Actl

Sets the internal torque limit for negative torque reference values. The internal negative motor torque will not be
allowed to exceed this value.

Default:
Min/Max:
Units:

-1.0
-8.0/0.0
P.U.

RO

Real

125

Torque Pos Limit

Sets the external torque limit for positive torque reference values. The external positive motor torque will not be
allowed to exceed this value.

Default:
Min/Max:
Units:

2.0000
0.0000/8.0000
P.U.

Y

RW Real

126

Torque Neg Limit

Sets the external torque limit for negative torque reference values. The external negative motor torque will not be
allowed to exceed this value.

Default:
Min/Max:
Units:

-2.0000
-8.0000/0.0000
P.U.

Y

RW Real

127

Mtring Power Lim

Sets the maximum motoring (positive) power of the drive. This can be calculated by multiplying the desired
maximum motor torque and the maximum motor speed. A value of 1.0 = nominal motor power.

Default:
Min/Max:
Units:

8.0000
0.0000/8.0000
P.U.

Y

RW Real

128

Regen Power Lim

Sets the maximum regenerative (negative) power of the drive. This can be calculated by multiplying the desired
maximum motor torque and the maximum motor speed. A value of 1.0 = nominal motor power.
Note: The default value for this parameter was changed from -1.0000 to -0.5000 for firmware version 2.003.

Default:
Min/Max:
Units:

-0.5000
-8.0000/0.0000
P.U.

Y

RW Real

129

Atune Trq Ref

Sets the motor torque that is applied to the motor during the flux current and inertia tests.
Note: The minimum value for this parameter was changed from 0.2500 to 0.2000 for firmware version 2.003.

Default:
Min/Max:
Units:
Scale:

0.50
0.2/1.0
P.U.
1.0 = P.U. Motor to Torque

RW Real

130

Trq Ref TP Sel

Enter or write a value to select torque reference data displayed in

Par 131

[Trq Ref TP Data].

Note: The value for option 5 was changed to “Reserved” for firmware version 2.004.

Default:

Options:

0 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
15 =

“Zero”

“Zero”

16 = “Neg Lim Src”

“Scale Output”

17 = “MPwr Par Lim”

“Spd Torque”

18 = “RPwr Par Lim”

“Trq Mode Out”

19 = “+Trq ParLim”

“Actv TrqMode”

20 = “-Trq ParLim”

“Reserved”

21 = “Nom Bus Volt”

“Trq En Input”

22 = “Bus Volt Hys”

“NotchFiltOut”

23 = “Bus Reg Ref”

“NotchFilt In”

24 = “Bus Reg Err”

“Trq Lim In”

25 = “Bus Reg Intg”

“Bus Reg Out”

26 = “BusReg Clamp”

“Pos Pwr Lim”

27 = “BusRegOutput”

“Neg Pwr Lim”

28 = “IAA Filt Out”

“Pos Atun Trq”

29 = “IAA dVf/dt”

“Neg Atun Trq”

30 = “MC Trq Lim”

“Pos Lim Src”

31 = “IqActlTrqLim”

131

Trq Ref TP Data

Displays the data selected by

Par 130

[Trq Ref TP Sel].

Default:
Min/Max:
Units:
Scale:

0.0
-/+8.0 P.U.
P.U.
1.0 = P.U. Motor to Torque

RO

Real

Freq (Hz)

Attenuation

A

A