Him indication of a fault, Manually clearing faults, Fault and alarm types – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 144

Advertising
background image

144

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Chapter 3

Troubleshooting

HIM Indication of a Fault

The HIM also provides visual notification of a fault.

Manually Clearing Faults

Follow the steps to manually clear a fault:

1.

Press

(Esc) on the HIM to acknowledge the fault.

The fault information will be removed so that you can use the HIM.

2.

Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.

3.

After corrective action has been taken, clear the fault using one of the
methods:

Press

(Stop) on the HIM

Cycle drive power

Select “Clear Faults” from the Diagnostics > Faults menu on the HIM

Fault and Alarm Types

A fault is a condition that stops the drive. An alarm is a condition that, if left
untreated, may stop the drive. There are three configuration types for indicating a
fault and/or alarm.

Table 5 - Fault Type Descriptions

Condition

Display

Drive is indicating a fault.
The LCD HIM immediately reports the fault condition by displaying the
following:

“Faulted” appears in the status line

Fault number

Fault name

Time that has passed since the fault occurred
Press Esc to regain control of the HIM

F-> Faulted

Auto

0.0

Hz

Main Menu:

Diagnostics

Parameter

— Fault — F24

DC Bus Overvolt

Time since Fault

00:23:52

Esc

Type

Fault Description

1

Non-Configurable Fault

The cause of the fault must be corrected before the fault can be cleared.

2

User Configurable

Programming and commissioning personnel can configure the drive’s response to
the exception events. Response include:

Ignore

Alarm

Fault Coast Stop

Fault Ramp Stop

Fault Current Limit Stop

3

Non-Configurable Alarm Can only be configured as a alarm.

Advertising