Logic status word, Dpi device limitations, Logic status word dpi device limitations – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual
Page 163

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013
163
Application Notes
Appendix B
Logic Status Word
DPI Device Limitations
PowerFlex 700S drives use a 450 mA device on the 12V DPI power supply. Due
to the typical load of a external DPI device of 140 mA, there is a three DPI device
limit.
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status
Description
x Active
0 = Not Active
1 = Active
x
Running
0 = Not Running
1 = Running
x
Command
Direction
0 = Reverse
1 = Forward
x
Actual
Direction
0 = Reverse
1 = Forward
x
Accel
0 = Not Accelerating
1 = Accelerating
x
Decel
0 = Not Decelerating
1 = Decelerating
x
Jogging
0 = Not Jogging
1 = Jogging
x
Fault
0 = No Fault
1 = Fault
x
Alarm
0 = No Alarm
1 = Alarm
x
Flash Mode
0 = Not in Flash Mode
1 = In Flash Mode
x
Run Ready
0 = Not Ready to Run
1 = Ready to Run
x
At Limit
(1)
(1) See parameter 304 - [Limit Status] for a description of the limit status conditions.
0 = Not At Limit
1 = At Limit
x
Tach Loss Sw
0 = Not Tach Loss Sw
1 = Tach Loss Sw
x
At Zero Spd
0 = Not At Zero Speed
1 = At Zero Speed
x
At setpt Spd
0 = Not At Setpoint Speed
1= At Setpoint Speed
x
Enable
0 = Not Enabled
1 = Enabled