Parameter data in linear list format – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 33

Advertising
background image

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

33

Programming and Parameters

Chapter 2

Parameter Data in Linear List Format

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

1

Motor NP Volts

Set to the motor nameplate rated volts.

Default:
Min/Max:
Units:

Calculated

(1)

75/705
V

RW 16-bit

Integer

2

Motor NP FLA

Set to the motor nameplate rated full load amps. Range limited by three-second inverter rating.

Default:
Min/Max:
Units:

Calculated

(1)

Calculated/Calculated
A

RW Real

3

Motor NP Hertz

Set to the motor nameplate rated frequency.

Default:
Min/Max:
Units:

Calculated

(1)

2.0000/500.0000
Hz

RW Real

4

Motor NP RPM

Set to the motor nameplate rated rpm.

Default:
Min/Max:
Units:

Calculated

(1)

1/30000
rpm

RW 16-bit

Integer

5

Motor NP Power

Set to the motor nameplate rated power.
Note: The unit of measure for this parameter was changed from kW to Hp for firmware version 2.003.

Default:
Min/Max:
Units:

Calculated

(1)

0.2500/3500.0000
Hp

RW 32-bit

Integer

6

Mtr NP Pwr Units

The power units shown on the motor nameplate.

Default:

Options:

0 =

0 =
1 =

“Hp”

“Hp”
“kW”

7 Motor

Poles

Set the number of motor poles indicated on the motor nameplate or manufacturer's motor data sheet. Only even
numbers of poles are allowed.
Calculation: (120 x NP Hz) / NP rpm = Poles [round down]
Note: The maximum value was changed from 60 to 128 for firmware version 4.002.

Default:
Min/Max:
Units:

4
2/128
Pole

RW 16-bit

Integer

9

Total Inertia

Time, in seconds, for a motor coupled to a load to accelerate from zero to base speed, at rated motor torque.
Calculated during auto-tune.

Default:
Min/Max:
Units:

2.0000
0.0100/655.0000
s

Y

RW Real

10

Speed Ref 1

Sets the speed reference that the drive should use when selected by

Par 27

[Speed Ref A Sel] or

Par 28

[Speed Ref B Sel]. A value of 1.0 represents base speed of the motor.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

11

Spd Ref1 Divide

Par 10

[Speed Ref 1] is divided by this number. This number can be used to scale the value of Par 10 [Speed Ref 1].

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

12

Speed Ref 2

Sets the speed reference that the drive should use when selected by

Par 27

[Speed Ref A Sel]

or

Par 28

[Speed Ref B Sel]. A value of 1.0 represents base speed of the motor.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

13

Spd Ref2 Multi

Par 12

[Speed Ref 2] is multiplied by this number. This number can be used to scale the value of

Par 12 [Speed Ref 2].

Default:
Min/Max:

1.0000
-/+2200000000.0000

Y

RW Real

14

through

20

Preset Speed 1

through

Preset Speed 7

Provides an internal fixed speed command value. The preset speeds may be selected with

Par 27

[Speed Ref A Sel]

or

Par 28

[Speed Ref B Sel].

Default:
Min/Max:
Units:
Scale:

0.0000
-/+8.0000 P.U.
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

21

Speed Trim 1

Provides an additive trim value to

Par 38

[Speed Ref Scale].

Default:
Min/Max:
Units:
Scale:

0.0000
-/+14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

22

Speed Trim 2

Provides an additive speed trim value to

Par 47

[SpdRef + SpdTrm1] with a Lead/Lag filter. The Position regulator

output is linked to this parameter by default. This speed trim value affects the speed reference input to the speed
regulator.

Default:
Min/Max:
Units:
Scale:

0.0000
-/+14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

23

Speed Trim 3

Provides a scalable speed trim value that will be added to

Par 47

[SpdRef + SpdTrm1].

Par 24

[SpdTrim 3 Scale]

scales this value prior to the trim value affecting the speed reference.

Default:
Min/Max:
Units:
Scale:

0.0000
-/+14112.0000
rpm

Par 4

[Motor NP RPM] = 1.0 P.U.

Y

RW Real

24

SpdTrim 3 Scale

Par 23

[Speed Trim 3] is multiplied by this number. This number can be used to scale the value of

Par 23 [Speed Trim 3].

Default:
Min/Max:

1.0000
-/+1000.0000

Y

RW Real

25

STrim2 Filt Gain

Sets the lead term for the

Par 22

[Speed Trim 2] filter. Values greater than 1 will result in a lead function and value

less than 1 will result in a lag function. A value of 1 will disable the filter.

Default:
Min/Max:

1.0000
-/+15.0000

Y

RW Real

(1) The calculation is based on the drive frame size and input voltage.