343 OL

OpnLp

CurrLim

Displays the current limit set by the Open Loop Inverter Overload (OL) function. This function sets this current limit
based on stator current feedback and the current ratings of the drive - continuous and short term (three-second
rating). Typically the drive will have a sixty-second rating of 110% of continuous current and a three-second
rating at 150% of the continuous. Under normal operating conditions, the open loop function sets this current
limit to the short term (three-second) rating. If the function detects an overload, it lowers the limit to the
continuous level. After a period of time (typically one to three minutes), the function returns the limit to the short
term rating.

Default:
Min/Max:
Units:

8.0000
0.0000/8.0000
P.U.

RO

Real

344

OL ClsLp CurrLim

Displays the current limit set by the Closed Loop Inverter Overload (OL) function. This function will set a current
limit level based on the values in

Par 355

[Iq Ref Limited],

Par 313

[Heatsink Temp] and the thermal characteristics

of the drive. Under normal operating conditions, the function typically sets the limit at 250% of the continuous
drive rating. If the function determines that the power device junction temperature is approaching maximum, it
will reduce this limit to the level required to prevent additional heating of the inverter. This level could be as low
as the continuous rating of the drive. If the inverter temperature decreases, the function will raise the limit to a
higher level. Disable this protection by setting bit 13 “OL ClsLpDsbl” of

Par 153

[Control Options].

Default:
Min/Max:
Units:

8.0000
0.0000/8.0000
P.U.

RO

Real

345

Drive OL JnctTmp

Displays the calculated junction temperature of the power semiconductors in the inverter. The calculation uses the
values of

Par 313

[Heatsink Temp],

Par 355

[Iq Ref Limited], and inverter thermal characteristics contained in the

power EE memory. If this value exceeds the maximum junction temperature (visible in

Par 348

[Drive OL TP Data]

when

Par 347

[Drive OL TP Sel] option 12 “fJunTmprMax” is selected), two faults occur: Inverter Overtemperature

Fault (fault code 15), and Junction Overtemperature Fault - indicated by bit 7 “Jnc OverTemp” of

Par 346

[Drive OL

Status].

Default:
Min/Max:
Units:

0.0000
-50.0000/300.0000
°C

RO

Real

346

Drive OL Status

Indicates the status of various overload (OL) conditions.
• Bit 0 “NTC Shorted” indicates the Negative Temperature Coefficient (NTC) device has a short circuit.
• Bit 1 “NTC Open” indicates the NTC has an open circuit.
• Bit 2 “HS OverTemp” indicates heatsink temperature is above 105 °C for ratings 1.1…11.0 A, 115 °C for 14…34 A, 100 °C for 40…52 A.
• Bit 3 “HS Pending” indicates heatsink temperature is above 95C for ratings 1.1…11 A, 105 °C for 14…34 A, 90 °C for 40…52 A.
• Bit 4 “IT Trip” indicates the drive has exceed the 3 second rating of either the 150% normal duty rating or 200% of the heavy duty rating.
• Bit 5 “IT Pending” indicates the drive OL integrator is at 50% of the time out time.
• Bit 6 “IT Foldback” indicates the drive closed loop current limit is in a fold back condition. The value of the fold back is proportional to the calculated junction temperature.
• Bit 7 “Jnc Over Temp” indicates the junction temperature has exceeded the maximum temperature for the power semiconductor device.

347

Drive OL TP Sel

Enter or write a value to select the drive overload data displayed in

Par 348

[Drive OL TP Data].

Note: Value 44 “HH PwrBdTemp” was added for firmware version 2.004. Added values 45 “IGBT CndLoss”, 46 “IGBT
SwtLoss” and 47 “Fwd CndLoss” for firmware version 3.003.

Default:

Options:

0 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
15 =
16 =
17 =
18 =
19 =
20 =
21 =
22 =
23 =

“Zero”

“Zero”

24 = “fIgbtWatts”

“fAbsIsCurr”

25 = “iIgbtPerMod”

“fDelta”

26 = “fFdThres”

“fAbsIqCurr”

27 = “fFdSlope”

“fOL_l”

28 = “fFdJunCase”

“fOL_m”

29 = “fFdWatts”

“fOL_k”

30 = “fMaxHsDegc”

“fOL_g”

31 = “fCsImp”

“fOL_intg”

32 = “fCsFltr”

“fCL_intg”

33 = “fPwmHz”

“fInvOLClim”

34 = “fElecHz”

“fJuncDegc”

35 = “fModIdex”

“fJunTmprMax”

36 = “fBoost”

“f60sPUCur”

37 = “fTotalWatts”

“f60sAmp”

38 = “fHSDegc”

“f3sPUCur”

39 = “iAdconv”

“f3sAmp”

40 = “Jct Temp”

“fRatioInvMtr”

41 = “Jct Tmp HiHp”

“fRatioMtrInv”

42 = “Jct Tmp Fwd“

“iConvertStat”

43 = ”HH Loss Intg”

“fIgbtThres”

44 = “HH PwrBdTemp”

“fIgbtSlope”

45 = “IGBT CndLoss”

“fIgbtEnergy”

46 = “IGBT SwtLoss”

“fIgbtJuncase”

47 = “Fwd CndLoss”

348

Drive OL TP Data

Displays the value selected by

Par 347

[Drive OL TP Sel].

Default:
Min/Max:

0.0000
-/+2200000000.0000

RO

Real

350

Iq Actual Ref

Displays the value of motor current reference that is present at the output of the divide by flux calculation.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO

Real

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Jnc

O

ver

Te

mp

IT F

oldback

IT P

ending

IT T

rip

HS P

ending

HS O

ve

rT

emp

NT

C Open

NT

C Shor

te

d

Default

x

x

x

x

x

x

x

x

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True

Advertising