Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 99

Advertising
background image

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

99

Programming and Parameters

Chapter 2

No.

Name
Description

Values

Li

nk

ab

le

Re

ad

-W

ri

te

Da

ta

T

ype

626

to

646

To DriveLogix00

to

To DriveLogix20

These parameters display the output values communicated from the PowerFlex 700S drive to the DriveLogix
controller.

Default:
Min/Max:

0
-/+32 (dependant on

Par 625

[To DL DataType])

Y

RO Set by Par

625

650

DPI In DataType

Sets the data type for each word communicated from an external controller to the PowerFlex 700S drive via a DPI communication module. Setting a bit high will configure the associated word as a
Real data type and setting the bit low will configure it for Integer data type.

651

652

653

654

655

656

657

658

DPI Data In A1

DPI Data In A2

DPI Data In B1

DPI Data In B2

DPI Data In C1

DPI Data In C2

DPI Data In D1

DPI Data In D2

These parameters display the input values communicated from DPI communication modules to the PowerFlex
700S drive.

Default:
Min/Max:

0
-/+32 (dependant on

Par 650

[DPI In

DataType])

RO 32-bit

Integer

659

DPI Out DataType

Sets the data type for each word communicated from the PowerFlex 700S drive to an external controller via a DPI communication module. Setting a bit high will configure the associated word as a
Real data type and setting the bit low will configure it for Integer data type.

660

661

662

663

664

665

666

667

DPI Data Out A1

DPI Data Out A2

DPI Data Out B1

DPI Data Out B2

DPI Data Out C1

DPI Data Out C2

DPI Data Out D1

DPI Data Out D2

These parameters display the output values communicated from the PowerFlex 700S drive to DPI communication
modules.

Default:
Min/Max:

0
-/+32 (dependant on

Par 659

[DPI Out

DataType])

Y

RW Set by Par

659

669

Write Mask

Enables/disables write access (parameters, links, etc.) for DPI ports. Changes to this parameter only become effective when power is cycled, the drive is reset or bit 15 “Security” of

Par 712

[Write

Mask Act], transitions from “1” to “0.”
Note: This parameter was added for firmware version 3.001.

Options

DP

I D2

Re

al

DP

I D1

Re

al

DP

I C2 R

eal

DP

I C1 R

eal

DP

I B

2 Re

al

DP

I B

1 Re

al

DP

I A2 R

ea

l

DP

I A1 R

ea

l

Default

0

0

0

0

0

0

0

0

Bit

7

6

5

4

3

2

1

0

0 = False
1 = True

Options

DPI

D2 R

ea

l

DPI

D1 R

ea

l

DPI

C2 Re

al

DPI

C1 Re

al

DPI

B2

Rea

l

DPI

B1

Rea

l

DPI

A2 R

eal

DPI

A1 R

eal

Default

0

0

0

0

0

0

0

0

Bit

7

6

5

4

3

2

1

0

0 = False
1 = True

Options

Dr

iv

eL

og

ix

Re

se

rv

ed

In

t D

PI C

omm

Re

se

rv

ed

Au

x DP

I C

on

n

Ex

t DPI C

onn

Lo

ca

l H

IM

Te

rm

in

al

B

lk

Default

1

1

1

x

1

1

1

1

Bit

7

6

5

4

3

2

1

0

0 = False
1 = True

Advertising