Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

81

Programming and Parameters

Chapter 2

429

Ids Integ Freq

Sets the break frequency of the flux producing (d-axis) current regulator. This and

Par 430

[Ids Reg P Gain]

determine the integral gain for the d-axis current regulator. Set by the autotune procedure. Do not change
this value.

Default:
Min/Max:
Units:

10
0/32767
rad/s

RW 16-bit

Integer

430

Ids Reg P Gain

Sets the proportional gain of the flux producing (d-axis) current regulator. Set by the autotune procedure. Do
not change this value.

Default:
Min/Max:
Scale:

1.0
0.0/100.0
x 10

RW 16-bit

Integer

431

Test Current Ref

Sets the current reference used for Motor Control (MC) Test Mode.

Units:
Default:
Min/Max:
Scale:

%
50.0
0.0/799.9
x 10

RW 16-bit

Integer

432

Test Freq Ref

Sets the frequency reference used for Motor Control (MC) Test Mode.
Note: The default value was changed for firmware version 2.003.

Default:
Min/Max:
Units:
Scale:

1.0
-/+799.9
%
x 10

RW 16-bit

Integer

433

Test Freq Rate

Sets the rate of change of frequency reference used for Motor Control (MC) Test Mode.

Default:
Min/Max:
Units:
Scale:

5.0
0.0/1000.0
%/s
x 10

RW 16-bit

Integer

434 Mtr

Vds

Base

Displays the motor flux producing (d-axis) voltage command when running at nameplate motor speed and
load. This value is determined during the auto-tune procedure. Do not change this value. Used only in FOC
modes.

Default:
Min/Max

0
-8192/0

RO

16-bit
Integer

435 Mtr

Vqs

Base

Displays the motor torque producing (q-axis) voltage command when running at nameplate motor speed and
load. This value is determined during the auto-tune procedure. Do not change this value. Used only in FOC
modes.

Default:
Min/Max:

0
0/8192

RO

16-bit
Integer

437 Vqs

Max

Displays the maximum torque producing (q-axis) voltage allowed on the motor. Adaptation is disabled below
this voltage. This value is determined during the auto-tune procedure. Do not change this value. Used only in
FOC modes.

Default:
Min/Max:

7971
0/32767

RW 16-bit

Integer

438 Vds

Max

Displays the maximum flux producing (d-axis) voltage allowed on the motor. Adaptation is disabled below
this voltage. This value is determined during the auto-tune procedure. Do not change this value. Used only in
FOC modes.

Default:
Min/Max:

5793
0/32767

RW 16-bit

Integer

439 Vqs

Min

Displays the minimum torque producing (q-axis) voltage required for motor control adaptation. This value is
determined during the auto-tune procedure. Do not change this value. Used only in FOC modes.

Default:
Min/Max:

246
-/+32767

RW 16-bit

Integer

440 Vds

Min

Displays the minimum flux producing (d-axis) voltage required for motor control adaptation. Adaptation is
disabled below this voltage. This value is determined during the auto-tune procedure. Do not change this
value.

Default:
Min/Max:

246
-/+32767

RW 16-bit

Integer

441 Vds

Fdbk

Filt

Displays measured filtered motor flux producing (d-axis) voltage.

Default:
Min/Max:

0
-/+32767

RO

16-bit
Integer

442 Vqs

Fdbk

Filt

Displays measured filtered motor torque producing (q-axis) voltage.

Default:
Min/Max:

0
-/+32767

RO

16-bit
Integer

443

Flux Reg P Gain1

Sets the Proportional (P) gain for the flux regulator. Do not change this value.

Default:
Min/Max:

150
0/32767

RW 16-bit

Integer

444

Flux Reg I Gain

Sets the Integral (I) gain for the flux regulator. Do not change this value.

Default:
Min/Max:

350
0/32767

RW 16-bit

Integer

445

Slip Gain Max

Displays the maximum slip frequency allowed in the motor control. The scaling is in hertz x 256. This value is
determined during the auto-tune procedure. Do not change this value.

Default:
Min/Max:
Units:

300
100/10000
%

RW 16-bit

Integer

446

Slip Gain Min

Displays the minimum slip frequency allowed in the motor control. The scaling is in hertz x 256. This value is
determined during the auto-tune procedure. Do not change this value.

Default:
Min/Max:
Units:

50
0/100
%

RW 16-bit

Integer

447

Slip Reg P Gain

Sets the Proportional (P) gain for the slip regulator. Do not change this value.

Default:
Min/Max:

35
0/32767

RW 16-bit

Integer

448

Slip Reg I Gain

Sets the Integral (I) gain for the slip regulator. Do not change this value.

Default:
Min/Max:

100
0/32767

RW 16-bit

Integer