Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

115

Programming and Parameters

Chapter 2

841

Anlg Out2 Offset

Provides an offset for Analog Output 2 before the scaling and limit blocks in the Analog Output 2 function. This
parameter value is summed with either

Par 839

[Anlg Out2 DInt] or

Par 840

[Anlg Out2 Real] at the beginning of

the function.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

842

Anlg Out2 Scale

Scales the range of the source parameter to the range of Analog Output 2. For example: If

Par 838

[Anlg Out2 Sel]

is set to 1 “Output Freq”, the output frequency of the drive is 0 - 60Hz and you enter “6” in this parameter,

Par 844

[Anlg Out2 Value] = 6Hz per 1V, or 0 - 60Hz.

Par 839

[Anlg Out2 DInt] or

Par 840

[Anlg Out2 Real] is multiplied by this number after the limit function.

Note: The turn-off point for this parameter has been changed from ±0.001 to ±0.0001 for firmware version
4.002.

Default:
Min/Max:
Units:

0.0000
-/+2200000000.0000
/V

Y

RW Real

843

Anlg Out2 Zero

Applies an offset to the scaled value of Analog Output 2. This parameter is summed with the output of the
scaling block. This sum produces

Par 844

[Anlg Out2 Value]. Typically this value corresponds to 0V for Analog

Output 2.

Default:
Min/Max:
Units:

0.0000
-/+20.0000
V

Y

RW Real

844

Anlg Out2 Value

Displays the voltage reference for Analog Output 2 before the digital to analog conversion.

Default:
Min/Max:
Units:

0.0000
-/+10.0000
V

RO Real

845

Dig Out1 Sel

identifies the signal used on Digital Output 1. If the desired signal is not available in the selection list, choose
option 0 - “User Select” and link with

Par 846

[Dig Out1 Data] and

Par 847

[Dig Out1 Bit] to select the desired

parameter and bit for output.

Default:

Options:

3 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =

“Ready”

“User Select”

15 = “Torque Limit”

“Not Fault”

16 = “Power Limit”

“Not Alarm”

17 = “Fault”

“Ready”

18 = “Alarm”

“Running”

19 = “Command Dir”

“Reserved”

20 = “Actual Dir”

“Reserved”

21 = “Jogging”

“Enable On”

22 = “In Position”

“Active”

23 = “Posit Watch1”

“At Speed”

24 = “Posit Watch2”

“At Setpt 1”

25 = “Cmpr 1 A</=B”

“Above Setpt 2”

26 = “Cmpr 1 A>/=B”

“At ZeroSpeed”

27 = “Cmpr 2 A</=B”

“Speed Limit”

28 = “Cmpr 2 A>/=B”

“CurrentLimit”

846

Dig Out1 Data

Link a word to this parameter that will control Digital Output 1. The bit within the selected word that will control
Digital Output 1 is set by

Par 847

[Dig Out1 Bit].

Default:
Min:
Max:

00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111

Y

RW 32-bit

Boolean

847

Dig Out1 Bit

Selects the bit, from the word linked to

Par 846

[Dig Out1 Data], that will change the status of Digital Output 1

(e.g., when Par 847 [Dig Out1 Bit] equals 0, bit 0 of Par 846 [Dig Out1 Data] will control Digital Output 1).

Default:
Min/Max:

0
-32/31

Y

RW 16-bit

Integer

848

Dig Out1 On Time

Defines the amount of time between a False to True transition on the output status and the corresponding
change in state of Digital Output 1. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or digital output will not change state. Par 848 [Dig Out1 On Time]
can be disabled by setting the delay time to 0 (zero).
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:
Units:

0.00
0.00/600.00
s

RW 16-bit

Integer

849

Dig Out1 OffTime

Defines the amount of time between a True to False transition on the output status and the corresponding
change in state of Digital Output 1. If a transition on an output condition occurs and starts the time delay and the
output condition returns to its original state before the delay timer reaches the setpoint, the delay timer will be
aborted and the corresponding output status or digital output will not change state.
Note: This parameter was added for firmware version 3.001.

Default:
Min/Max:
Units:

0.00
0.00/600.00
s

RW 16-bit

Integer

850

Dig Out2 Sel

Identifies the signal used on Digital Output 2. If the desired signal is not available in the selection list, choose
option 0 - “User Select” and link with

Par 851

[Dig Out 2 Data] and

Par 852

[Dig Out2 Bit] to select the desired

parameter and bit for output.

Default:

Options:

8 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =

“Active”

“User Select”

15 = “Torque Limit”

“Not Fault”

16 = “Power Limit”

“Not Alarm”

17 = “Fault”

“Ready”

18 = “Alarm”

“Running”

19 = “Command Dir”

“Reserved”

20 = “Actual Dir”

“Reserved”

21 = “Jogging”

“Enable On”

22 = “In Position”

“Active”

23 = “Posit Watch1”

“At Speed”

24 = “Posit Watch2”

“At Setpt 1”

25 = “Cmpr 1 A</=B”

“Above Setpt 2”

26 = “Cmpr 1 A>/=B”

“At ZeroSpeed”

27 = “Cmpr 2 A</=B”

“Speed Limit”

28 = “Cmpr 2 A>/=B”

“CurrentLimit”

851

Dig Out2 Data

Link a word to this parameter that will control Digital Output 2. The bit within the selected word that will control
Digital Output 2 is set by

Par 852

[Dig Out2 Bit].

Default:
Min:
Max:

00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111

Y

RW 32-bit

Boolean

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e