Par 177 – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 47

Advertising
background image

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

47

Programming and Parameters

Chapter 2

177

Setpt 2 Limit

Creates a tolerance - hysteresis band around the value in

Par 176

[Setpt2 TripPoint].

For positive setpoints:
• Turn-on level = TripPoint
• Turn-off level = TripPoint - Limit.
For negative setpoints:
• Turn-on level = TripPoint
• Turn-off level = TripPoint + Limit.

Default:
Min/Max:
Units:

0.0100
0.0000/0.5000
P.U.

Y

RW Real

178

PI TP Sel

Enter or write a value to select Process Control PI data displayed by

Par 179

[PI TP Data].

The values for options 1 & 8 were changed to “Reserved” for firmware version 2.004.

Default:

Options:

0 =

0 =
1 =
2 =
3 =
4 =
5 =
6 =

“Zero”

“Zero”

7 = “Status Hold”

“Reserved”

8 = “Reserved”

“LPF Output”

9 = “Reset Status”

“P Gain Term”

10 = “Time Axis En”

“Reg Output”

11 = “Enbl Status”

“On Intg Lim”

12 = “Out Max Lim”

“On Out Limit”

13 = “Out Min Lim”

179

PI TP Data

Displays the data selected by

Par 178

[PI TP Sel].

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO

Real

180

PI Output

The final output of the Process Control regulator. A value of 1 can represent either base motor speed, motor rated
torque, or 100% for some external function.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO

Real

181

PI Reference

The reference input for the process control regulator. A value of 1 can represent either base motor speed, motor
rated torque, or 100% for some external function.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

Y

RW Real

182

PI Feedback

The feedback input for the process control regulator. A value of 1 can represent either base motor speed, motor
rated torque, or 100% for some external function.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

Y

RW Real

183

PI Error

Displays the error of the process trim reference minus the process trim feedback.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO

Real

184

PI Lpass Filt BW

Sets the bandwidth of a single pole filter applied to the error input of the Process Control regulator. The input to
the filter is the difference between

Par 181

[PI Reference] and

Par 182

[PI Feedback]. The output of this filter is

used as the input to the process control regulator.

Default:
Min/Max:
Units:

0.0000
0.0000/500.0000
rad/s

Y

RW Real

185

PI Preload

Presets the integrator of the Process Control regulator.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

Y

RW Real

186

PI Prop Gain

Controls the proportional gain of the Process Control regulator. If the proportional gain is 1.0, the regulator output
equals 1 P.U. for 1 P.U. error.

Default:
Min/Max:

8.0000
0.0000/200.0000

Y

RW Real

187

PI Integ Time

Controls the integral gain of the Process Control regulator. If the integrator time is 1.0, the regulator output equals
1 P.U. in 1 second for 1 P.U. error.

Default:
Min/Max:
Units:

8.0000
0.0000/4000.0000
/s

Y

RW Real

188

PI Integ HLim

The high limit of the integral gain channel for the Process Control regulator. A value of 1 can represent either base
motor speed, motor rated torque, or 100% for some external function.

Default:
Min/Max:
Units:

0.1000
0.0000/8.0000
P.U.

Y

RW Real

189

PI Integ LLim

The low limit of the integral gain channel for the Process Control regulator. A value of 1 can represent either base
motor speed, motor rated torque, or 100% for some external function.

Default:
Min/Max:
Units:

-0.1000
-8.0000/0.0000
P.U.

Y

RW Real

190

PI Integ Output

Displays the output value of the integral channel of the Process Control regulator. A value of 1 can represent either
base motor speed, motor rated torque, or 100% for some external function.

Default:
Min/Max:
Units:

0.0000
-/+8.0000 P.U.
P.U.

RO

Real

191

PI High Limit

The high limit of the Process Control regulator output. A value of 1 can represent either base motor speed, motor
rated torque, or 100% for some external function.

Default:
Min/Max:
Units:

0.1000
0.0000/8.0000
P.U.

Y

RW Real

192

PI Lower Limit

The low limit of the Process Control regulator output. A value of 1 can represent either base motor speed, motor
rated torque, or 100% for some external function.

Default:
Min/Max:
Units:

-0.1000
-8.0000/0.0000
P.U.

Y

RW Real

196

ParamAccessLevel

The value of this parameter establishes the level of parameter access for the Human Interface Module (HIM).
• Value 0 - Basic grants access to the minimum number of parameters
• Value 1 - Advanced grants access to a larger group of parameters

Default:

Options:

0 =

0 =
1 =

“Basic”

“Basic”
“Advanced”

RW 16-bit

Integer

201

Language

Selects the display language when using an LCD HIM. Currently, only option 0 - “English” is available.

Default:

Options:

0 =

0 =
1 =

“English”

“English”
“Alt Language”

RW 16-bit

Integer

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e