Programming and Parameters

Chapter 2

571

Trend In1 Real

Provides real input to the Trend 1. The Trending function samples this parameter for Trend Buffer 1, if bit 1 “In 1
Real” is set.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

572

Trend Out1 DInt

Displays the output for Trend Buffer 1, if the buffer is using integer data. This will equal the value of the
element, in Trend Buffer 1, specified by

Par 569

[TrendBuffPointer].

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

573

Trend Out1 Real

Displays the output for Trend Buffer 1, if the buffer is using real data. This will equal the value of the element,
in Trend Buffer 1, specified by

Par 569

[TrendBuffPointer].

Default:
Min/Max:

0.0000
-/+2200000000.0000

RO Real

574

Trend In2 DInt

Provides integer input to the Trend 2. The Trending function samples this parameter for Trend Buffer 2, if bit 2
“In 2 Real” is cleared.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

575

Trend In2 Real

Provides real input to the Trend 2. The Trending function samples this parameter for Trend Buffer 2, if bit 2 “In 2
Real” is set.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

576

Trend Out2 DInt

Displays the output for Trend Buffer 2, if the buffer is using integer data. This will equal the value of the
element, in Trend Buffer 2, specified by

Par 569

[TrendBuffPointer].

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

577

Trend Out2 Real

Displays the output for Trend Buffer 2, if the buffer is using real data. This will equal the value of the element,
in Trend Buffer 2, specified by

Par 569

[TrendBuffPointer].

Default:
Min/Max:

0.0000
-/+2200000000.0000

RO Real

578

Trend In3 DInt

Provides integer input to the Trend 3. The Trending function samples this parameter for Trend Buffer 3, if bit 3
“In 3 Real” is cleared.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

579

Trend In3 Real

Provides real input to the Trend 3. The Trending function samples this parameter for Trend Buffer 3, if bit 3 “In 3
Real” is set.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

580

Trend Out3 DInt

Displays the output for Trend Buffer 3, if the buffer is using integer data. This will equal the value of the
element, in Trend Buffer 3, specified by

Par 569

[TrendBuffPointer].

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

581

Trend Out3 Real

Displays the output for Trend Buffer 3, if the buffer is using real data. This will equal the value of the element,
in Trend Buffer 3, specified by

Par 569

[TrendBuffPointer].

Default:
Min/Max:

0.0000
-/+2200000000.0000

RO Real

582

Trend In4 DInt

Provides integer input to the Trend 4. The Trending function samples this parameter for Trend Buffer 4, if bit 4
“In 4 Real” is cleared.

Default:
Min/Max:

0
-/+2147483648

Y

RW 32-bit

Integer

583

Trend In4 Real

Provides real input to the Trend 4. The Trending function samples this parameter for Trend Buffer 4, if bit 4 “In 4
Real” is set.

Default:
Min/Max:

0.0000
-/+2200000000.0000

Y

RW Real

584

Trend Out4 DInt

Displays the output for Trend Buffer 4, if the buffer is using integer data. This will equal the value of the
element, in Trend Buffer 4, specified by

Par 569

[TrendBuffPointer].

Default:
Min/Max:

0
-/+2147483648

RO 32-bit

Integer

585

Trend Out4 Real

Displays the output for Trend Buffer 4, if the buffer is using real data. This will equal the value of the element,
in Trend Buffer 4, specified by

Par 569

[TrendBuffPointer].

Default:
Min/Max:

0
-/+2200000000.0000

RO Real

586

IdsCmd Slew Rate

Defines the slew rate for the torque producing voltage (Vqs) regulator. The output variation is limited by one
count every Par 586 / 16 sec.
Notes: This value should not be changed. This parameter was added for firmware version 4.001.

Default:
Min/Max:
Units:

5.000
0.000/16.383
s

RW Real

587

SlipReg Err Lmt

Defines the error level at which the slip regulator input becomes active. When the error level reaches the value
specified in this parameter and the error count condition (specified in

Par 589

[Err Count Lmt]) is met, the drive

control will transition from the slew rate limit mode to normal operation of the slip regulator.
Notes: This value should not be changed. This parameter was added for firmware version 4.001.

Default:
Min/Max:

0
+/-32767

RW 16-bit

Integer

588

VqsReg Err Lmt

Defines the error level at which the Flux Producing Voltage (Vqs) regulator input becomes active. When the
error level reaches the value specified in this parameter and the error count condition (specified in

Par 589

[Err

Count Lmt]) is met, the drive control will transition from the slew rate limit mode to normal operation of the
Vqs regulator.
Notes: This value should not be changed. This parameter was added for firmware version 4.001.

Default:
Min/Max:

0
+/-32767

RW 16-bit

Integer

589

Err Count Lmt

Defines the control loop counts limit, where the counter counts up if the error level of the Vqs regulator input is
equal to the error level during Flux Producing Current (Ids) command Slew Rate operation. When the counter
exceeds the value of this parameter then the normal Vqs regulator operation becomes active. The same limit of
control loop counts is applied to the Slip Slew Rate operation, where the counter counts up if the error level of
the Slip regulator input is equal to the error level during Slip Slew Rate operation. When the counter exceeds
the value of this parameter then the normal Slip regulator operation becomes active.
Notes: This value should not be changed. This parameter was added for firmware version 4.001.

Default:
Min/Max:

0
+/-32767

RW 16-bit

Integer

No.

Name
Description

Values

Link

able

Re

ad

-Write

Da

ta

T

yp

e