Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Programming Manual User Manual

Page 148

Advertising
background image

148

Rockwell Automation Publication 20D-PM001C-EN-P - July 2013

Chapter 3

Troubleshooting

43

VoltageFdbk Loss

2

A loss of motor or DC Bus voltage feedback has occurred because of a
communication failure between Motor Control and Voltage Feedback board.

Check the communication line between Motor

Control (MC) and the Voltage Feedback board.

Replace the Voltage Feedback board.
Configured with

Par 394

[VoltFdbkLossCnfg].

44

Runtime Data Rst

3

Runtime data (hours, energy) has been reset to zero due to a checksum error. (Informational Only)

45

Enable Health

1

The safety circuit is active.

Check the input signal to the safety circuit.

46

Interp Out Synch

2

The interpolator for position feedback lost synchronization with the Velocity
Position Loop (VPL).

Configured with

Par 378

[Interp Flt Cnfg].

47

MC CML Task Fail

3

The Current Minor Loop (CML) task has been delayed or run with an incorrect
interval.

Cycle power to the drive.

48

No Ctrl Device

1

The controlling device (HIM or controller) has been disconnected while the
drive was running.

Check the controlling device connections to the drive.

49

DPI Loss Port 1

2

The device at DPI port 1 has stopped communicating with the drive.
A SCANport device is connected to a drive operating DPI devices at 500k Baud.

Verify that the DPI device is present and functional at
port 1.
Configured with

Par 391

[DPI CommLoss Cfg].

50

DPI Loss Port 2

2

The device at DPI port 2 has stopped communicating with the drive.
A SCANport device is connected to a drive operating DPI devices at 500k Baud.

Verify that the DPI device is present and functional at
port 2.
Configured with

Par 391

[DPI CommLoss Cfg].

51

DPI Loss Port 3

2

The device at DPI port 3 has stopped communicating with the drive.
A SCANport device is connected to a drive operating DPI devices at 500k Baud.

Verify that the DPI device is present and functional at
port 3.
Configured with

Par 391

[DPI CommLoss Cfg].

52

DPI Loss Port 4

2

The device at DPI port 4 has stopped communicating with the drive.
A SCANport device is connected to a drive operating DPI devices at 500k Baud.

Verify that the DPI device is present and functional at
port 4.
Configured with

Par 391

[DPI CommLoss Cfg].

53

DPI Loss Port 5

2

The device at DPI port 5 has stopped communicating with the drive.
A SCANport device is connected to a drive operating DPI devices at 500k Baud.

Verify that the DPI device is present and functional at
port 5.
Configured with

Par 391

[DPI CommLoss Cfg].

54

DPI Loss Port 6

2

The device at DPI port 6 has stopped communicating with the drive.
A SCANport device is connected to a drive operating DPI devices at 500k Baud.

Verify that the DPI device is present and functional at
port 6.
Configured with

Par 391

[DPI CommLoss Cfg].

55

Net Loss DPI P1

2

A communications fault has occurred between the communication adapter at
DPI port 1 and the network.

Verify the network connection.
Verify the status of network.
Configured with

Par 392

[NetLoss DPI Cnfg].

56

Net Loss DPI P2

2

A communications fault has occurred between the communication adapter at
DPI port 2 and the network.

Verify the network connection.
Verify the status of network.
Configured with

Par 392

[NetLoss DPI Cnfg].

57

Net Loss DPI P3

2

A communications fault has occurred between the communication adapter at
DPI port 3 and the network.

Verify the network connection.
Verify the status of network.
Configured with

Par 392

[NetLoss DPI Cnfg].

58

Net Loss DPI P4

2

A communications fault has occurred between the communication adapter at
DPI port 4 and the network.

Verify the network connection.
Verify the status of network.
Configured with

Par 392

[NetLoss DPI Cnfg].

59

Net Loss DPI P5

2

A communications fault has occurred between the communication adapter at
DPI port 5 and the network.

Verify the network connection.
Verify the status of network.
Configured with

Par 392

[NetLoss DPI Cnfg].

60

Net Loss DPI P6

2

A communications fault has occurred between the communication adapter at
DPI port 6 and the network.

Verify the network connection.
Verify the status of network.
Configured with

Par 392

[NetLoss DPI Cnfg].

61

Logix Out of Run

2

The DriveLogix controller is in a Non-Run mode. Non-Run modes include
program, remote-program and faulted modes.

Clear the fault.
Configured with

Par 386

[Lgx OutOfRunCnfg].

62

Logix Timeout

2

The communication connection to the DriveLogix controller has timed out.

Configured with

Par 387

[Lgx Timeout Cnfg].

63

Logix Closed

2

The DriveLogix controller has closed the Controller to Drive connection.

Verify that the Drive is present in the Controller I/O
configuration.
Configured with

Par 388

[Lgx Clod Cnfg].

64

Logix Link Chng

2

A required link in the Controller to Drive Communication Format has been
modified.

Clear the fault.
Configured with

Par 389

[Lgx LinkChngCnfg].

65

HiHp In PhaseLs

2

(High Horse Power Only)
AC Input Phase Loss - the AC input phase voltage has fallen.

Check for voltage on each AC input phase.

Check the status of each external AC input fuse.
Configured with

Par 370

[HiHp InPhsLs Cfg].

No.

Name

Type

(1)

Description

Action